Inspection Detail
Inspection: 315282897 - R.R. Donnelley
Inspection Information - Office: Nv-E-Reno 0953210
Site Address:
R.R. Donnelley
14100 Lear Blvd.
Reno, NV 89506
Mailing Address:
, , 00000
Union Status: NonUnion
SIC:2754
NAICS: 323111/Commercial Gravure Printing
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 06/20/2011
Planning Guide: Safety-Manufacturing
Emphasis: S:Mfg 2392-2952
Case Closed: 06/20/2011
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 102270287 |
Investigation Summary
On April 25, 2011, Employee #1 and a coworker, had begun bringing a firetube boiler back online after performing an annual inspection. The boiler was filled with preheated feed water supplied by a deaerator tank. The boiler had not been started up at the time of the accident. Employee #1 was a trainee working under the direct supervision of a coworker, an experienced boiler technician. The coworker noticed one of six handhole covers leaking on the boiler. Employee #1 was instructed to tighten the handhole to stop the leak. Employee #1 used an eight inch crescent wrench to tighten the nut on the stud bolt on the handhole cover. After the leak stopped, Employee #1 was instructed to tighten the other handhole covers a small amount. Employee #1 was tightening the last handhole cover when the stud bolt failed. The cover plate slid down on the inside of the boiler which allowed the hot water to flow out of the opening and into the face of Employee #1. Employee #1 was transported to a local Medical Center and later transported by air to the regional burn center. Employee #1 suffered second and third degree burns on his face, chest, and shoulders.
Keywords: BURN, WRENCH, BOILER, FACE, WATER
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 315282897 | Hospitalized injury | Burn/Scald(Heat) | Occupation not reported |