Powered by GoogleTranslate

Inspection Detail

Inspection: 315091009 - Electric Shop, Inc. Dba Mr. Electric Of Miami & Jo

Inspection Information - Office: Wichita Area Office

 

Inspection Nr: 315091009
Report ID: 0729700
Date Opened: 08/30/2011

Site Address:
Electric Shop, Inc. Dba Mr. Electric Of Miami & Jo
300 S. Webster
Spring Hill, KS 66083

Mailing Address:
1001 N. Peral St., Paola, KS 66071

Union Status: NonUnion

SIC:1731

NAICS: 238210/Electrical Contractors


Inspection Type: Complaint

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/31/2011

Emphasis: S:Electrical

Case Closed: 12/19/2013


Related Activity
Type Activity Nr Safety Health
Complaint 208078204 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $4,200 $0 $0 $0 $0 $4,200
Current Penalty $3,000 $0 $0 $0 $0 $3,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260095 A 10/28/2011 11/02/2011 $3,000 $4,200 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 201345857
Event: 08/27/2011
Employee Is Burned in Arc Flash

On August 27, 2012, Employee #1 and Coworkers #1 and #2 were working as electricians. The assignment was to replace the breaker panel 480-volt AC supply cables that ran between the 7200/480 volt transformer and the breaker panel. The employees had replaced all three phases with four cables per phase. As the cables were being replaced, the transformer and breaker panel were deenergized. After the cables had been replaced, power was turned back on to the transformer by the utility so voltage checks could be performed at the breaker panel. Employee #1 used his meter to check the voltages and was putting the cover back on the breaker panel over the terminal lugs when the cover slipped and contacted the energized lugs and created an arc flash. Employee #1 was burned on the hands and forearms. The main breaker tripped when the short occurred. Emergency services were called and Employee #1 was taken to Kansas University Medical Center for treatment of his burns.

Keywords: BURN, ELECTRIC ARC, ELECTRICAL WORK, LOCKOUT, ELECTRICAL CABINET, ARM, HAND

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 315091009 Hospitalized injury Burn/Scald(Heat) Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close