Powered by GoogleTranslate

Inspection Detail

Inspection: 314862772 - Uc Los Angeles

Inspection Information - Office: Los Angeles District Office

 

Inspection Nr: 314862772
Report ID: 0950641
Date Opened: 08/01/2012

Site Address:
Uc Los Angeles
10833 Le Conte Ave.
Los Angeles, CA 90095

Mailing Address:
501 Westwood Plz., 4th Flr., Los Angeles, CA 90095

Union Status: Union

SIC:8221

NAICS: 611310/ Colleges, Universities, and Professional Schools


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: StateGovt

Safety/Health: Safety

Close Conference: 10/18/2012

Emphasis:

Case Closed: 12/21/2013


Related Activity
Type Activity Nr Safety Health
Accident 102761004
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1 2
Current Violations 2 2
Initial Penalty $5,850 $0 $0 $5,850 $0 $11,700
Current Penalty $0 $0 $0 $2,250 $0 $2,250
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 23200002 A04 11/30/2012 12/05/2012 $1,125 $5,850 $0 12/21/2012 F - Formal Settlement  
2. 02001 Other 23900041 A 11/30/2012 12/05/2012 $1,125 $5,850 $0 12/21/2012 F - Formal Settlement  

Investigation Summary

Investigation Nr: 202544086
Event: 07/27/2012
Burn - Electrical Fault in Panel

At 1:30 p.m. on Friday, July 27, 2012, Employee #1 was working as an electrician for the University of California at Los Angeles, or UCLA. He was at the ground floor of the old UCLA hospital building, which was being refurbished and repaired. Two days earlier, the same employee had connected cord sets, also known as extension cords, to an electrical panel to supply temporary power to a demolition crew. The panel had not been used for some time, since the hospital was not operational. At about 1:30 p.m. on that Friday, some electricians were assigned to reenergize the panel. One group of electricians was at an air station to turn power on to the panel, while two electricians were on the floor checking to see if the panel had been energized. Employee #1 was one of the electricians on the floor. He was using a Fluke tester to check on the uppermost left breaker. According to an eyewitness, Employee #1 inserted the probes of the tester into the breaker and had to move some of the wires out of the way. The eyewitness saw small sparks at the bottom of the panel followed by a flash fire and explosion. The witness was able to move away from the flash. According to Employee #1, he was not wearing hand gloves. When he inserted the probes, he saw the flash fire and explosion but he was unable to move fast enough to avoid the flash. He sustained burns on both arms and hands. Initially, the burns were deemed first- and second-degree burns. He was taken to UCLA's hospital. Over the weekend, the burns deteriorated to third-degree burns, and Employee #1 was taken to the Grossman Burn Center in West Hills. According to a report made by the employer, the two electricians removed the cover of the circuit breaker and then tested the panel to see if it was energized. Photos taken by the employer after the accident, however, showed the circuit breaker without a cover.

Keywords: BURN, E GI II, ELECTRIC ARC, PROTECTIVE CLOTHING, ELECTRICAL, PPE, ELECTRICIAN, GROUND FAULT, ELECTRICAL CABINET, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 314862772 Hospitalized injury Burn/Scald(Heat) Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.