Powered by GoogleTranslate

Inspection Detail

Inspection: 314827296 - Bergelectric Corporation

Inspection Information - Office: Van Nuys District Office

 

Inspection Nr: 314827296
Report ID: 0950643
Date Opened: 10/25/2011

Site Address:
Bergelectric Corporation
43a Second Floor "C" Bldg 1 Grand Ave
San Luis Obispo, CA 93407

Mailing Address:
5650 W. Centinela Ave., Los Angeles, CA 90045

Union Status: NonUnion

SIC:1731

NAICS: 238210/Electrical Contractors


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 02/22/2012

Emphasis: S:Construction (Cship)

Case Closed: 12/14/2012


Related Activity
Type Activity Nr Safety Health
Accident 102779048
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $0 $0 $0 $600 $0 $600
Current Penalty $0 $0 $0 $600 $0 $600
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 1509 A 02/26/2012 03/07/2012 $600 $600 $0 03/05/2012 F - Formal Settlement  

Investigation Summary

Investigation Nr: 202470878
Event: 10/10/2011
Employee Falls from Ladder after Electric Shock

At 2:30 p.m. on October 10, 2011, Employee #1 was installing recessed lighting on the second floor of a building. A supervisor reportedly deenergized the power to a 277 volt line hanging from the ceiling. Employee #1 positioned a 10 ft ladder to access the installation area. He climbed the ladder and used a one-week-old Milwaukee electrical proximity tester to test the insulated covered wire. Employee #1 did not get a reading from the tester. While holding the cable coming from a "J" box in his left hand, he pulled off the scrap sheath with his right hand. Employee #1 contacted an energized 277 volt wire, fell from the ladder, and landed on his back and head. After evaluation at Med Stop Urgent Care, Employee #1 was hospitalized at Sierra Vista Hospital for unspecified fracture(s).

Keywords: ELEC INSULATION, FRACTURE, HEAD, ELECTRIC CABLE, ELECTRICAL TESTING, LADDER, LIGHTING FIXTURE, LOCKOUT, ELECTRIC SHOCK, FALL

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 314827296 Hospitalized injury Fracture Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.