Powered by GoogleTranslate

Inspection Detail

Inspection: 314771288 - Gmc Services, Llc

Inspection Information - Office: Baton Rouge Area Office

 

Inspection Nr: 314771288
Report ID: 0625700
Date Opened: 06/15/2011

Site Address:
Gmc Services, Llc
221 Venture Way
Lafayette, LA 70507

Mailing Address:
3850 Causeway Blvd., Metarie, LA 70002

Union Status: Union

SIC:1711

NAICS: 238220/ Plumbing, Heating, and Air-Conditioning Contractors


Inspection Type: Accident

Scope: Partial

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 11/04/2011

Emphasis:

Case Closed: 12/20/2017


Related Activity
Type Activity Nr Safety Health
Accident 102656642
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2 4
Current Violations 2 2 4
Initial Penalty $12,600 $0 $0 $1,800 $0 $14,400
Current Penalty $6,300 $0 $0 $900 $0 $7,200
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100333 A01 11/17/2011 12/06/2011 $6,300 $6,300 $0 12/09/2011 A - Amendment  
2. 01002 Serious 19100335 A01 I 11/17/2011 12/06/2011 $0 $6,300 $0 12/09/2011 F - Formal Settlement  
3. 02001 Other 19040032 B02 II 11/17/2011 12/06/2011 $0 $900 $0 12/09/2011 A - Amendment  
4. 02002 Other 19040032 B02 II 11/17/2011 12/06/2011 $900 $900 $0 12/09/2011 A - Amendment  

Investigation Summary

Investigation Nr: 200556546
Event: 06/14/2011
Electric Shock - Direct Contact with Energized Conductor

Two employees were repairing the compressor on a Trane air conditioning unit installed on the roof of a building. The unit had two compressors and was capable of running at 50 percent of full power. The employees had not deenergized the air conditioning unit at the panelboard, but the unit's switch was open while they dismantled the broken compressor. One of the workers removed the coil wire for the old compressor, and the employees closed the unit's switch. The workers set the new compressor in place, but did not connect the wiring to the compressor before they took a break. After the break, one of the workers began to connect the new compressor by removing electrical tape from the wiring. He contacted an energized 277-volt conductor and was electrocuted.

Keywords: COMPRESSOR, E GI IV, ELECTRICAL, AIR CONDITIONER, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 314771288 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close