Powered by GoogleTranslate

Inspection Detail

Inspection: 314620030 - Amercable, Inc.

Inspection Information - Office: Little Rock Area Office

 

Inspection Nr: 314620030
Report ID: 0627100
Date Opened: 07/31/2010

Site Address:
Amercable, Inc.
350 Bailey Rd.
El Dorado, AR 71730

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:3357

NAICS: 335929/Other Communication and Energy Wire Manufacturing


Inspection Type: Accident

Scope: Partial

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 11/16/2010

Emphasis: S:Electrical

Case Closed: 02/01/2011


Related Activity
Type Activity Nr Safety Health
Accident 100265693
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $12,600 $0 $0 $0 $0 $12,600
Current Penalty $11,000 $0 $0 $0 $0 $11,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19100132 D02 01/03/2011 02/05/2011 $5,500 $6,300 $0 I - Informal Settlement  
2. 01001B Serious 19100335 A01 IV 01/03/2011 02/05/2011 $0 $0 $0 I - Informal Settlement Citation has been deleted.
3. 01002A Serious 19100333 A01 01/03/2011 02/05/2011 $5,500 $6,300 $0 I - Informal Settlement  
4. 01002B Serious 19100333 B02 IIA 01/03/2011 02/05/2011 $0 $0 $0 I - Informal Settlement  
5. 01002C Serious 19100333 B02 IIB 01/03/2011 02/05/2011 $0 $0 $0 I - Informal Settlement  
6. 01002D Serious 19100333 C01 01/03/2011 02/05/2011 $0 $0 $0 I - Informal Settlement Citation has been deleted.

Investigation Summary

Investigation Nr: 200263911
Event: 07/30/2010
Employee Suffers Electrical Shock and Is Killed

On or about July 30, 2010, Employee #1, an electrical test technician, was leaning over or downward to place completed pass/fail inspection reports in plastic bags. The plastic bags were attached to the outside of the reels, near the arbor holes of wire which had previously undergone an, 8,000 volt, AC Voltage Withstand Test. His head came in contact with the tip of an ungrounded conductor and insulation compounds. Employee #1 suffered a fatal electric shock. The path to ground was the employee's head through his left foot.

Keywords: HEAD, ELECTROCUTED, ELECTRIC SHOCK, FOOT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 314620030 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.