Inspection Detail
Inspection: 314182130 - Lighting Technologies, Lp/ Lit
Inspection Information - Office: Dallas Area Office
Site Address:
Lighting Technologies, Lp/ Lit
3515 Lion'S Lair
Greenville, TX 75402
Mailing Address:
301 W. Arlington Ave., Fort Worth, TX 76110
Union Status: NonUnion
SIC:3641
NAICS: 335110/Electric Lamp Bulb and Part Manufacturing
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 04/20/2011
Emphasis:
Case Closed: 11/16/2011
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 100785203 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 7 | 7 | ||||
| Current Violations | 6 | 1 | 7 | |||
| Initial Penalty | $33,600 | $0 | $0 | $0 | $0 | $33,600 |
| Current Penalty | $22,960 | $0 | $0 | $3,920 | $0 | $26,880 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19260021 B02 | 10/05/2011 | 10/13/2011 | $3,920 | $4,900 | $0 | I - Informal Settlement | ||
| 2. | 01002 | Other | 19260056 A | 10/05/2011 | 10/11/2011 | $3,920 | $4,900 | $0 | I - Informal Settlement | ||
| 3. | 01003 | Serious | 19260095 A | 10/05/2011 | 10/11/2011 | $3,920 | $4,900 | $0 | I - Informal Settlement | ||
| 4. | 01004 | Serious | 19260100 A | 10/05/2011 | 10/11/2011 | $3,360 | $4,200 | $0 | I - Informal Settlement | ||
| 5. | 01005 | Serious | 19260301 A | 10/05/2011 | 10/10/2011 | $3,920 | $4,900 | $0 | I - Informal Settlement | ||
| 6. | 01006 | Serious | 19260416 A01 | 10/05/2011 | 10/11/2011 | $3,920 | $4,900 | $0 | I - Informal Settlement | ||
| 7. | 01007 | Serious | 19261053 B13 | 10/05/2011 | 10/11/2011 | $3,920 | $4,900 | $0 | I - Informal Settlement |
Investigation Summary
On April 12, 2011, Employee #1, an apprentice and permanent employee, was working for his employer, Lighting Technologies, LP, which had been contracted to retrofit lighting fixtures for Greenville High School in Greenville, TX. The job involved converting 48 175-watt mercury vapor can lights to 24-watt compact florescent lights. The operation involved eliminating the ballast from the existing can fixtures and taking existing power and wiring directly to the can socket. Employee #1 was assigned to perform the work in the attic utility crawl space at the outdoor canopy, on a live, 277-volt circuit. He was not provided with personal protective equipment (PPE). During removal of the old ballast, Employee #1 cut the wires, using wire strippers without insulating handles in his bare hands. Employee #1 was electrocuted and killed.
Keywords: BALLAST--LIGHTING, ELEC INSULATION, PPE, ELECTROCUTED, LOCKOUT, INEXPERIENCE, ELECTRIC SHOCK, HAND TOOL
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 314182130 | Fatality | Electric Shock | Occupation not reported |
Translate