Powered by GoogleTranslate

Inspection Detail

Inspection: 314024324 - M & L Services Co

Inspection Information - Office: Wichita Area Office

 

Inspection Nr: 314024324
Report ID: 0729700
Date Opened: 03/04/2010

Site Address:
M & L Services Co
1202 Country Club Lane, Apt F3
Junction City, KS 66441

Mailing Address:
904 E. 4th Street, Junction City, KS 66441

Union Status: NonUnion

SIC:1711

NAICS: 238220/ Plumbing, Heating, and Air-Conditioning Contractors


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 04/09/2010

Emphasis:

Case Closed: 03/11/2013


Related Activity
Type Activity Nr Safety Health
Accident 101345569
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 6 1 7
Current Violations 6 1 7
Initial Penalty $23,550 $0 $0 $1,500 $0 $25,050
Current Penalty $9,950 $0 $0 $1,300 $0 $11,250
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19101200 E01 05/05/2010 02/10/2011 $250 $750 $0 05/26/2010 F - Formal Settlement  
2. 01002 Serious 19101200 H 05/05/2010 02/10/2011 $250 $750 $0 05/26/2010 F - Formal Settlement  
3. 01003 Serious 19260020 B01 05/05/2010 02/10/2011 $450 $1,050 $0 05/26/2010 F - Formal Settlement  
4. 01004 Serious 19260021 B05 05/05/2010 02/10/2011 $3,000 $7,000 $0 05/26/2010 F - Formal Settlement  
5. 01005 Serious 19260152 F03 05/05/2010 05/10/2010 $3,000 $7,000 $0 05/26/2010 F - Formal Settlement  
6. 01006 Serious 19260152 E02 05/05/2010 02/10/2011 $3,000 $7,000 $0 05/26/2010 F - Formal Settlement  
7. 02001 Other 19040039 A 05/05/2010 05/10/2010 $1,300 $1,500 $0 05/26/2010 F - Formal Settlement  

Investigation Summary

Investigation Nr: 201345287
Event: 03/03/2010
Employee Sustains Burns in Flash Fire, Later Dies

At approximately 2:50 p.m. on March 3, 2010, Employee #1, a plumber, was working with a coworker installing new furnaces and AC units at an apartment complex. The furnace and AC units were all the same design and configuration. They were flushing the existing .375 in. diameter copper lines of R22 refrigerant oil residue in preparation for the new 410 refrigerant. The coworker was outside injecting the flammable liquid solvent into the line, and Employee #1 was inside the apartment reclaiming the cleaning solvent mixture utilizing a plastic coffee container. During this process, the vapors from the solvent ignited (flash fire), and the employee sustained second and third degrees burns to 80% of his body. Employee #1 died several hours later at a local Hospital. It was believed that the flash fire was a resulted from static as the liquid was discharging out of the copper line into the plastic coffee can. Cleaning the lines involved one person injecting a combination of "Virginia 10" solvent and nitrogen into the existing copper lines using a "Pro-Flush" injection system from the exterior of the structure and a second person on the inside to reclaim the product at the end of the lines. The "Pro-Flush injection cylinder contained approximately 24 oz of the "Virginia 10 (Class IB flammable liquid) degreasing solvent and an unknown quantity of nitrogen. The "Pro-Flush" injection system was purchased from a vendor who was selling products to plumbing companies for use in complying with the new EPA rules for R410 refrigerant. The "Pro-Flush" device was originally purchased by the company and included a can of nonflammable solvent. The employer decided not to use the solvent originally purchased with the system and began to use the Virginia 10, recommended by another company selling the products for plumbers to be used for cleaning refrigerant lines being converted to R410 refrigerant.

Keywords: BURN, VAPOR, AIR CONDITIONER, CLEANING, FIRE, REFRIGERANT, PLUMBING

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 314024324 Fatality Burn/Scald(Heat) Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close