Inspection Detail
Inspection: 313878670 - Davco Electrical Contractors Corporation
Inspection Information - Office: Jacksonville Area Office
Site Address:
Davco Electrical Contractors Corporation
5425 South Williamson Blvd
Port Orange, FL 32129
Mailing Address:
4885 Park Ridge Blvd, Boynton Beach, FL 33426
Union Status: NonUnion
SIC:1731
NAICS: 238210/Electrical Contractors
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 10/07/2010
Emphasis: S:Commercial Constr, S:Electrical, S:Powered Ind Vehicle, S:Struck-By
Case Closed: 09/26/2012
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 101358166 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 2 | 2 | ||||
Current Violations | 2 | 2 | ||||
Initial Penalty | $5,775 | $0 | $0 | $0 | $0 | $5,775 |
Current Penalty | $5,775 | $0 | $0 | $0 | $0 | $5,775 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 19260416 A01 | 03/03/2011 | 03/15/2011 | $4,900 | $4,900 | $0 | - | ||
2. | 01002 | Serious | 19260417 A | 03/03/2011 | 03/15/2011 | $875 | $875 | $0 | - |
Investigation Summary
A contractor on a construction site had broken an underground section of electric cable. The electrical contractor on site was asked to repair the wiring to restore lighting in the parking areas. The general contractor's superintendent deenergized the line. Two employees working for the electrical contractor dug up the cable and tested the line to ensure that it was deenergized. The employees spliced the conductors, and the line was reenergized so that they could check the circuit voltage. The test indicated a problem, and the employees were going to continue troubleshooting by energizing and testing one conductor at a time. When one of the two workers went to deenergize a conductor, the other worker reached into the ground with his bare hand, grabbed the energized cable, and was electrocuted. The outer insulation on the cable was damaged, exposing the conductor.
Keywords: ELEC INSULATION, ELECTRICAL, UNDRGRD POWER LINE, ELECTRICIAN, ELECTROCUTED, LOCKOUT, E C, ELEC PROTECT EQUIP, ELECTRICAL WORK
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 313878670 | Fatality | Electric Shock | Electricians |