Inspection Detail
Inspection: 313820599 - Aee Tecnica De Cayey
Inspection Information - Office: Pr-E-Caguas 0257220
Site Address:
Aee Tecnica De Cayey
Carr 31 Km 57.2 Bo Montellano
Cayey, PR 00737
Mailing Address:
Po Box 372828, Cayey, PR 00737
Union Status: Union
SIC:4911
NAICS: 221122/Electric Power Distribution
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: StateGovt
Safety/Health: Safety
Close Conference: 12/28/2010
Emphasis:
Case Closed: 01/10/2013
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 101720464 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 5 | 1 | 6 | |||
Current Violations | 5 | 1 | 6 | |||
Initial Penalty | $35,000 | $0 | $0 | $0 | $0 | $35,000 |
Current Penalty | $5,000 | $0 | $0 | $0 | $0 | $5,000 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 19100269 A03 | 01/05/2011 | 01/31/2011 | $0 | $7,000 | $0 | 01/20/2011 | D - Govt Dismissed | |
2. | 01002 | Serious | 19100269 C01 | 01/05/2011 | 01/31/2011 | $0 | $7,000 | $0 | 01/20/2011 | D - Govt Dismissed | |
3. | 01003 | Serious | 19100269 M02 I | 01/05/2011 | 01/31/2011 | $5,000 | $7,000 | $0 | 01/20/2011 | F - Formal Settlement | |
4. | 01004 | Serious | 19100269 M03 II | 01/05/2011 | 01/31/2011 | $0 | $7,000 | $0 | 01/20/2011 | F - Formal Settlement | |
5. | 01005 | Serious | 19100269 O02 I | 01/05/2011 | 01/31/2011 | $0 | $7,000 | $0 | 01/20/2011 | D - Govt Dismissed | |
6. | 02001 | Other | 19040029 B01 | 01/05/2011 | 01/31/2011 | $0 | $0 | $0 | 01/20/2011 | F - Formal Settlement |
Investigation Summary
An employee made contact with a fuse riser that was energized by device T-7, which was closed instead of open. He and his coworkers were unaware that the fuse riser was energized at 4,800 volts. It was being fed inversely from bottom to top and not from the primary elctric line. The employee was electrocuted.
Keywords: E GI V, ELEC PROTECT EQUIP, E GI IV, ELECTRICAL, ELECTRIC SWITCH, ELECTRICIAN, ELECTROCUTED, ELEC UTILITY WORK
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 313820599 | Fatality | Electric Shock | Electrical power installers and repairers |