Powered by GoogleTranslate

Inspection Detail

Inspection: 313641631 - Aes Redondo Beach Llc

Inspection Information - Office: Long Beach District Office

 

Inspection Nr: 313641631
Report ID: 0950635
Date Opened: 09/29/2010

Site Address:
Aes Redondo Beach Llc
1100 N Harbor Dr
Redondo Beach, CA 90277

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:4911

NAICS: 221122/Electric Power Distribution


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 03/04/2011

Emphasis:

Case Closed: 01/14/2012


Related Activity
Type Activity Nr Safety Health
Accident 101032456
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 5 5
Current Violations 2 2
Initial Penalty $0 $0 $0 $3,700 $0 $3,700
Current Penalty $0 $0 $0 $1,075 $0 $1,075
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 23200002 A03 03/04/2011 03/04/2011 $0 $750 $0 03/24/2011 D - Govt Dismissed Citation has been deleted.
2. 01002 Other 23200002 A04 03/04/2011 03/04/2011 $0 $750 $0 03/24/2011 D - Govt Dismissed Citation has been deleted.
3. 01003 Other 23200002 A06 03/04/2011 03/04/2011 $0 $750 $0 03/24/2011 D - Govt Dismissed Citation has been deleted.
4. 01004 Other 23200003 03/04/2011 04/06/2011 $750 $1,125 $0 03/24/2011 F - Formal Settlement  
5. 01005 Other 23400017 A 03/04/2011 04/06/2011 $325 $325 $0 03/24/2011 W - Empr Withdrew  

Investigation Summary

Investigation Nr: 202530382
Event: 09/09/2010
Burn - Electrical Fault in Circuit Breaker Cubicle

An electric utility plant equipment operator and a coworker were performing a water-side tagout operation for a tube repair scheduled for the following day. They entered the generating unit's relay room. After opening circuit breaker Number 1507-2, the operator hung a tag on the 480-volt circuit breaker cubicle and moved on to circuit breaker cubicle Number 1507-1. As the operator reached that cubicle, he saw that the cubicle door was open. He reached into the cubicle and removed the control fuse and one of the three main fuses with his unprotected left hand. As he was removing the second main fuse, it contacted the top side of the third main fuse and fuse holder, causing an electrical fault. The ensuing electric arc burned the operator on his left hand, wrist, and forearm. The coworker responded to the arc flash by grabbing a carbon monoxide fire extinguisher and fighting the electrical fire with the help of the operator. As they fought the fire, a second fault occurred within the main feeder distribution cell. The operator was hospitalized with second-degree burns to his left wrist and forearm.

Keywords: BURN, FUSE, ELEC PROTECT EQUIP, ELECTRIC ARC, ELECTRICAL, PPE, E PTD, CIRCUIT BREAKER, ELEC UTILITY WORK, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 313641631 Hospitalized injury Burn/Scald(Heat) Power plant operators
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close