Inspection Detail
Inspection: 313508442 - Butterfly Wendel Us, Inc. Dba Deutsch Ecd
Inspection Information - Office: San Bernardino District Office
Site Address:
Butterfly Wendel Us, Inc. Dba Deutsch Ecd
5733 West Whittier Avenue
Hemet, CA 92545
Mailing Address:
, , 00000
Union Status: NonUnion
SIC:3629
NAICS: 335999/All Other Miscellaneous Electrical Equipment and Component Manufacturing
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 09/28/2010
Planning Guide: Safety-Manufacturing
Emphasis: L:Arrastim
Case Closed: 02/11/2011
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 102612223 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 1 | 2 | 3 | |||
Current Violations | 1 | 2 | 3 | |||
Initial Penalty | $18,000 | $0 | $0 | $560 | $0 | $18,560 |
Current Penalty | $2,700 | $0 | $0 | $560 | $0 | $3,260 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Other | 3203 A03 | 09/28/2010 | 10/29/2010 | $185 | $185 | $0 | - | ||
2. | 01002 | Other | 3314 G02 | 09/28/2010 | 10/29/2010 | $375 | $375 | $0 | - | ||
3. | 02001 | Serious | 23200004 A02 | 09/28/2010 | 10/11/2010 | $2,700 | $18,000 | $0 | 10/12/2010 | F - Formal Settlement |
Investigation Summary
At approximately 3:15 a.m. on April 7, 2010, Employee #1 was going to replace a 100-amp main fuse of a 3 phase 480-volt, Circuit Breaker Box #2, located in the Electrical Power room. The circuit breaker was connected to an Electrical Lighting Panel (LPB) powering the lighting systems of Molding & Assembly Departments of the manufacturing facility. He opened the circuit breaker cover and checked the continuity of the fuses utilizing a Fluke multi-meter tester. He determined that one of the three fuses were "Bad", which was replaced on April 6, 2010, in 2nd shift. He was in the process of replacing the fuse by using a non-conductive Buss Fuse Puller (Manufacturing Little Fuse, Model Number #FP-3) without deenergizing the circuit breaker when it started sparking causing electrical flash injuring him seriously. Employee #1 suffered burn injuries of his face and right lower arm. Employee #1 was taken to Arrowhead Regional Medical Center for treatment. Employee #1 was hospitalized for five days. The employer reported the serious injury accident to the Division at 8:31 a.m. on April 7, 2010.
Keywords: BURN, FUSE, ELECTRIC ARC, MAINTENANCE, ELECTRICIAN, MECHANIC, CIRCUIT BREAKER, FLASHBACK, ARM, FACE
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 313508442 | Hospitalized injury | Burn/Scald(Heat) | Machinery maintenance occupations |