Powered by GoogleTranslate

Inspection Detail

Inspection: 313165821 - Db Enterprises

Inspection Information - Office: Santa Ana District Office

 

Inspection Nr: 313165821
Report ID: 0950631
Date Opened: 06/10/2010

Site Address:
Db Enterprises
18621 Brookhurst St
Fountain Valley, CA 92708

Mailing Address:
10805 Artesia Blvd., Ste 102, Cerritos, CA 92708

Union Status: NonUnion

SIC:3599

NAICS: 332710/Machine Shops


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/24/2010

Emphasis:

Case Closed: 05/04/2013


Related Activity
Type Activity Nr Safety Health
Accident 102590635
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 3 4
Current Violations 1 3 4
Initial Penalty $10,800 $0 $0 $5,350 $0 $16,150
Current Penalty $7,560 $0 $0 $600 $0 $8,160
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 342 A 10/04/2010 10/07/2010 $500 $5,000 $0 11/01/2010 F - Formal Settlement  
2. 01002 Other 3203 A04 10/04/2010 10/07/2010 $50 $175 $0 11/01/2010 F - Formal Settlement  
3. 01003 Other 3400 C 10/04/2010 10/07/2010 $50 $175 $0 11/01/2010 F - Formal Settlement  
4. 02001 Serious 23200002 A 10/04/2010 10/07/2010 $7,560 $10,800 $0 11/01/2010 F - Formal Settlement  

Investigation Summary

Investigation Nr: 202551768
Event: 06/02/2010
Electrical Flash Burns

On June 2, 2010, Employee #1 was attempting to remove a three phase, three pole breaker from an energized buss bar assembly. Employee #1 was holding the breaker with his left hand while at the same time attempting to loosen the top screw on the right side of the breaker with his right hand, using a flat head screwdriver. When the top screw was completely removed from the threads, the breaker rotated to the left, allowing the three metal mounting poles to short between the three poles of the breaker mounted on the opposite side of the switchboard. This electrical short caused an intense arc flash, resulting in a severe burn injury to the left hand of Employee #1.

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 313165821 Hospitalized injury Burn/Scald(Heat) Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close