Powered by GoogleTranslate

Inspection Detail

Inspection: 312752249 - Anchor Mechanical, Inc.

Inspection Information - Office: Chicago North Area Office

 

Inspection Nr: 312752249
Report ID: 0524200
Date Opened: 12/05/2008

Site Address:
Anchor Mechanical, Inc.
656 Pearson St.
Des Plaines, IL 60016

Mailing Address:
215 S. Aberdeen, Chicago, IL 60607

Union Status: Union

SIC:1711

NAICS: 238220/ Plumbing, Heating, and Air-Conditioning Contractors


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Health

Close Conference: 05/29/2009

Emphasis:

Case Closed: 10/28/2009


Related Activity
Type Activity Nr Safety Health
Accident 101263705
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 1 1
Initial Penalty $7,000 $0 $0 $0 $0 $7,000
Current Penalty $2,000 $0 $0 $0 $0 $2,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19101000 A02 06/02/2009 07/20/2009 $3,500 $3,500 $0 06/16/2009 F - Formal Settlement Citation has been deleted.
2. 01001B Serious 19101000 E 06/02/2009 07/20/2009 $0 $0 $0 06/16/2009 F - Formal Settlement Citation has been deleted.
3. 01002A Serious 5A0001 06/02/2009 07/20/2009 $2,000 $3,500 $0 06/16/2009 F - Formal Settlement  
4. 01002B Serious 19101000 E 06/02/2009 07/20/2009 $0 $0 $0 06/16/2009 F - Formal Settlement  

Investigation Summary

Investigation Nr: 201262433
Event: 12/05/2008
Employee Is Overcome by Carbon Monoxide, Later Dies

On December 5, 2008, Employee #1 was dispatched to the site to perform normal maintenance on the building's boiler equipment. Two domestic heating boilers and three comfort heating boilers were located in the room. Employee #1 was working alone in the room. An employee of a cleaning service entered the boiler room at approximately 10:00 a.m. to get a ladder and observed that Employee #1 was sweating profusely and the room was extremely warm. At 11:00 a.m. an employee of the building management company tried to reach the victim by phone and did not receive a response. Between 11:30 a.m. and 12:00 p.m. on December 5, 2008, the victim's supervisor arrived at the site (also, after trying to reach him by phone) and found the door to the boiler room locked. At approximately 12:00 p.m. Employee #1 was found unresponsive in a boiler room of a condominium complex. Employee #1's supervisor reported that one of the three comfort heating boilers was operating. When the supervisor obtained the key to the room, he found Employee #1 sitting on the floor leaning against a box unconscious. Employee #1 was pronounced dead at 12:25 p.m. at the scene. The medical examiner called the fire department and requested that carbon monoxide measurements be taken in the boiler room. The fire department measured approximately 1,400 parts-per-million of carbon monoxide in the room. Exhaust dampers on two of the comfort heating boilers were observed by the contractor to be partially closed during troubleshooting following the accident. This included the damper on the boiler that was operating when Employee #1's supervisor entered the boiler room. Following an autopsy, the medical examiner declared Employee #1 died of carbon monoxide intoxication.

Keywords: UNCONSCIOUSNESS, ASPHYXIATED, HEATER, BOILER, CARBON MONOXIDE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 312752249 Fatality Asphyxia Machinery maintenance occupations
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close