Inspection Detail
Inspection: 312677263 - Rj Donovan Correctional Facility
Inspection Information - Office: San Diego District Office
Site Address:
Rj Donovan Correctional Facility
480 Alta Rd
San Diego, CA 92179
Mailing Address:
480 Alta Rd, San Diego, CA 92179
Union Status: Union
SIC:9223
NAICS: 922140/Correctional Institutions
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: StateGovt
Safety/Health: Safety
Close Conference: 04/09/2009
Emphasis:
Case Closed: 02/05/2019
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 101075471 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 1 | 11 | 12 | |||
Current Violations | 1 | 11 | 12 | |||
Initial Penalty | $3,375 | $0 | $0 | $7,420 | $0 | $10,795 |
Current Penalty | $2,700 | $0 | $0 | $4,535 | $0 | $7,235 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Other | 340 | 04/09/2009 | 05/27/2009 | $300 | $375 | $0 | 04/24/2009 | F - Formal Settlement | |
2. | 01002 | Other | 342 A | 04/09/2009 | 05/27/2009 | $3,000 | $5,000 | $0 | 04/24/2009 | F - Formal Settlement | |
3. | 01003 | Other | 23400012 A | 04/09/2009 | 05/27/2009 | $185 | $185 | $0 | 04/24/2009 | F - Formal Settlement | |
4. | 01004 | Other | 3272 C | 04/09/2009 | 05/27/2009 | $150 | $185 | $0 | 04/24/2009 | F - Formal Settlement | |
5. | 01005 | Other | 3314 G02 | 04/09/2009 | 05/27/2009 | $150 | $185 | $0 | 04/24/2009 | F - Formal Settlement | |
6. | 01006 | Other | 3314 H03 | 04/09/2009 | 05/27/2009 | $0 | $185 | $0 | 04/24/2009 | F - Formal Settlement | |
7. | 01007 | Other | 3314 J01 | 04/09/2009 | 05/27/2009 | $0 | $185 | $0 | 04/24/2009 | F - Formal Settlement | |
8. | 01008 | Other | 3329 A | 04/09/2009 | 05/27/2009 | $0 | $185 | $0 | 04/24/2009 | F - Formal Settlement | |
9. | 01009 | Other | 3329 B | 04/09/2009 | 05/27/2009 | $300 | $375 | $0 | 04/24/2009 | F - Formal Settlement | |
10. | 01010 | Other | 3382 A | 04/09/2009 | 05/27/2009 | $150 | $185 | $0 | 04/24/2009 | F - Formal Settlement | |
11. | 01011 | Other | 3384 A | 04/09/2009 | 05/27/2009 | $300 | $375 | $0 | 04/24/2009 | F - Formal Settlement | |
12. | 02001 | Serious | 3314 D | 04/09/2009 | 04/23/2009 | $2,700 | $3,375 | $0 | 04/24/2009 | F - Formal Settlement |
Investigation Summary
At approximately 11 p.m. on February 4, 2009, Employee #1 and Employee #2, both mechanics of R.J. Donovan Correctional Facility, were replacing the heating pump in Housing Unit Number 4 pump room. The seal on the old heat pump was leaking. This pump was part of the heating system that provided heat and hot water for showers to a building that houses inmates. Employee #1 removed the bolts that attached the pump to the cement floor. The small pump room was occupied with various hot water pipes, valves, and temperature gauges. The hot water pipe between the pump and the above heat exchanger were turn off and bled, but the remaining hot water pipes were kept on line. A temperature gauge (heavily impacted with calcium deposits on the outside) located next to the pump blew off while Employee #1 was located inside the pump room. Employee #1 never touched, bumped, or struck the temperature gauge with his body or tools. Employee #1 was sprayed with hot water (180 degrees F, 50 p.s.i.) from the hot water pipe, when the temperature gauge flew off. Employee #1 sustained second degree burns to his upper right hand and forearm, upper right thigh, abdomen, and a deep cut between his two middle fingers of his right hand that required stitches. He was hospitalized to treat his burns.
Keywords: BURN, FINGER, THIGH, HOT WATER TANK, RUPTURE, LACERATION, HAND
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 312677263 | Hospitalized injury | Burn/Scald(Heat) | Painters, construction and maintenance |