Inspection: 312676588 - Chula Vista Electric

Inspection Information - Office: San Diego District Office

 

Inspection Nr: 312676588
Report ID: 0950632
Date Opened: 12/30/2008

Site Address:
Chula Vista Electric
1010 2nd Ave
San Diego, CA 92101

Mailing Address:
127 Press Ln, Chula Vista, CA 91910

Union Status: Union

SIC:1731

NAICS: 238210/Electrical Contractors


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/19/2009

Emphasis:

Case Closed: 02/02/2010


Related Activity
Type Activity Nr Safety Health
Accident 101075125
Accident 101075133
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 1 3
Current Violations 2 2
Initial Penalty $40,500 $0 $0 $485 $0 $40,985
Current Penalty $0 $0 $0 $910 $0 $910
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 3203 A 06/22/2009 07/25/2009 $350 $485 $0 09/09/2009 F - Formal Settlement  
2. 02001 Serious 29400002 A 06/22/2009 07/07/2009 $0 $20,250 $0 09/09/2009 F - Formal Settlement Citation has been deleted.
3. 03001 Other 3382 A 06/22/2009 07/07/2009 $560 $20,250 $0 09/09/2009 F - Formal Settlement  

Investigation Summary

Investigation Nr: 201073277
Event: 12/27/2008
Two Workers Burned in an Arc Flash

On December 28, 2007, an electrical outage was affecting a portion of the building. Employee #1 and Employee #2 of Chula Vista Electric responded to the site to troubleshoot and repair the equipment causing the electrical outage. A worker led Employee #1 and #2 to an electrical room, where Employee #1 opened the 4,160-volt 3-phase OFC switch device. The OFC switching device contains three separate OFC switches, one switch for each electrical phase. The OFC device had a mechanical linkage that turns the internal fuses approximately a .25 turn. The turning of the fuse .25 turn disconnects the fuses from their contact points within the switch. The fuses are immersed in clear dielectric oil, which is intended to quench any electrical arc that may occur when the fuses are connected or disconnected from an energized electrical source. The three OFC switches are opened and closed simultaneously through the use of the mechanical linkage. Electrical power was still energized to the incoming (line) side of the fuse contact point within the OFC switches. Opening the OFC switch device deenergized the electrical power to the OFC fuses and to a malfunctioning transformer powered by the OFC switch device. As part of the troubleshooting process Employee #1 checked the fuses in the OFC switches. One fuse holder was removed completely and visually inspected. Employee #1 saw that the fuse was blown and noted that the dielectric oil within the switch was dark in color. Employee #1 placed the fuse holder on the floor and then raised the other two fuse holders and supported them on the fuse holder's alignment dowels that were located on the side of the fuse holder, partially suspending the fuse holder in the OFC switch. Employee #1 then assisted Employee #2 in inspecting the malfunctioning transformer unit. After assisting Employee #2 in the inspection of the transformer, Employee #1 returned to inspect the remaining two fuses in the OFC switches. To inspect the fuses Employee #1 had partially removed the fuse holder slightly from their suspended positions in the OFC switch. Employee #1 looked at the fuse to determine if the fuse was blown. Employee #1 then lowered the fuse holder back into the OFC switch suspending the fuse holders on the alignment dowel pins. After completing the inspection of the fuses, Employee #1 slightly rotated one of the fuse holders so that it would be better supported. Immediately after Employee #1 pulled his hand from the fuse holder he heard a "pop" sound. At that time an arc flash occurred within the OFC switch. This arc flash caused intense radiant heat and a short lived fire which expanded out of the OFC switch into the electrical room burning Employee #1 Employee #2 and the coworker who led them into the room. Employee #1 and #2 were hospitalized and suffered from unspecified burns as a result of the event.

Keywords: BURN, ELECTRIC ARC, ELECTRICAL VAULT, ELECTRICAL TESTING, ELECTRICIAN, ELECTRICAL WORK, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 312676588 Hospitalized injury Burn/Scald(Heat) Electricians
2 312676588 Hospitalized injury Burn/Scald(Heat) Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.