Inspection Information - Office: Monrovia District Office

 

Inspection Nr: 312665656
Report ID: 0950636
Date Opened: 01/11/2011

Site Address:
Henkels & Mccoy
720 Vail Ave
Montebello, CA 90640

Mailing Address:
2840 Ficus St, Pomona, CA 91766

Union Status: Union

SIC:1731

NAICS: 238210/Electrical Contractors


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/21/2011

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 04/20/2012


Related Activity
Type Activity Nr Safety Health
Accident 101809531
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $29,250 $0 $0 $0 $0 $29,250
Current Penalty $0 $0 $0 $4,800 $0 $4,800
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 1509 A 06/21/2011 07/01/2011 $4,800 $18,000 $0 07/05/2011 F - Formal Settlement  
2. 02001 Other 2943 E01 06/21/2011 07/01/2011 $0 $11,250 $0 07/05/2011 F - Formal Settlement  

Investigation Summary

Investigation Nr: 202477212
Event: 12/21/2010
Burn - Electrical Fault in Elbow

A four-person power line crew was replacing a transformer in a 6-meter-long, 2.1-meter-wide, 2.4-meter-deep underground vault. The transformer was in a bank, with another transformer, at the southwest corner of the vault. Six buses were located along the west wall between those two transformers and three other transformers in a bank at the northwest corner of the vault. Three of the employees were in the vault and a helper was outside. One employee, who was standing in front of the buses, contacted a cable elbow before it was disconnected from the bus and caused an electrical fault. The ensuing electric arc burned him and a second employee, who was standing between the buses and the two-transformer bank, mapping the wiring for the replacement transformer. The first injured employee suffered second- and third-degree burns on his face and neck and the back of his hands. The other injured employee suffered burns on his right ear, elbow, and hand. (The original form did not list the second injured worker on an injury line.)

Keywords: BURN, E GI II, ELECTRIC ARC, ELECTRICAL, POWER LINE WORKER, PPE, ELECTRIC CABLE, UNDRGRD INSTALLATION, ELEC UTILITY WORK, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 312665656 Hospitalized injury Burn/Scald(Heat) Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.