Site Address:
Southern California Edison
Big Tujunga Canyon Rd.
Tujunga, CA 91042

Mailing Address:
2244 Walnut Grove Ave., Rosemead, CA 91770

Union Status: Union

SIC:1731

NAICS: 238210/Electrical Contractors


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: LocalGovt

Safety/Health: Safety

Close Conference: 03/22/2010

Planning Guide: Safety-Construction

Emphasis:

Case Closed: 01/12/2011


Related Activity
Type Activity Nr Safety Health
Accident 102629987
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $18,000 $0 $0 $0 $0 $18,000
Current Penalty $2,700 $0 $0 $0 $0 $2,700
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 2941 D 03/24/2010 03/29/2010 $2,700 $18,000 $0 04/12/2010 F - Formal Settlement  

Investigation Summary

Investigation Nr: 202468559
Event: 09/25/2009
Two Employees Are Injured When Poll Topples Over

On September 25, 2009, a work crew of five employees (#1-#5) were assigned the task of removing high voltage transmission poles that were damaged during the Station Fire in Big Tujunga Canyon. Employee #5, the foreman, performed a tail gate briefing on the tear down of the damaged 40 foot wooden high voltage transmission pole and the company rules. Employee #4 performed a sound and visual inspection on the pole to be climbed by Employees #1 and #2. Employee #4 did not observe during his visual inspection a brand label on the pole that indicated the depth of the pole underneath the ground. Employees #1 and #2 climbed the pole and let down the transformer to the ground from the cross arm. Employees #1, #2 were approximately 30 feet in height on the pole when they began to bring down the conductor lines and upon letting down the second conductor line the pole fell over backwards with the Employees #1,#2 attached to the pole. Employees #3,#4,and #5 came to the assistance of the fallen Employees #1 and #2. The forest and fire department were called and Employees #1 and #2 were taken by helicopter to the Holy Cross Medical Center and then transferred to the Cedar Sinai Medical Center. Employee #1 was diagnosed with a fractured left arm and Employee #2 with a fractured pelvis, collar, and cheek bone. Employer is going to be cited for a serious accident related violation: T8CCR 2941(d) Work on or in Proximity to Overhead High Voltage lines.

Keywords: POWER LINE WORKER, FALL, TRANSMISSION TOWER

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 312434566 Hospitalized injury Fracture Electrical power installers and repairers
2 312434566 Hospitalized injury Fracture Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.