Inspection Detail
Inspection: 312000847 - Pulverdryer Usa Inc
Inspection Information - Office: Miosha General Industry Safety & Health Division
Site Address:
Pulverdryer Usa Inc
126 Avenue C
Springfield, MI 49037
Mailing Address:
, , 00000
Union Status: NonUnion
SIC:3567
NAICS: 333994/Industrial Process Furnace and Oven Manufacturing
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 01/31/2012
Planning Guide: Safety-Manufacturing
Emphasis: S:Enf Targeted
Case Closed: 03/29/2012
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 102461472 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 3 | 3 | ||||
| Current Violations | 3 | 3 | ||||
| Initial Penalty | $6,300 | $0 | $0 | $0 | $0 | $6,300 |
| Current Penalty | $2,520 | $0 | $0 | $0 | $0 | $2,520 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 40812179 | 03/09/2012 | 03/09/2012 | $840 | $2,100 | $0 | I - Informal Settlement | ||
| 2. | 01002 | Serious | 40812193 E | 03/09/2012 | 03/09/2012 | $840 | $2,100 | $0 | I - Informal Settlement | ||
| 3. | 01003 | Serious | 19100303 G02 II | 03/09/2012 | 03/09/2012 | $840 | $2,100 | $0 | I - Informal Settlement |
Investigation Summary
At approximately 10:15 a.m. on December 13, 2011, Employee #1, with Pulverdryer Usa Inc., was working with coworkers setting up a cyclone unit. Employee #1 was removing a product transfer tube with a powered industrial truck. While Employee #1 was doing this, the transfer tube fell off the forks and landed on the 480-volt cord to the cyclone unit which was suspended in the air at the time. Power to the cyclone was turned off during this incident. One of Employee #1's coworkers was observing the air lock which was not running. This coworker told Employee #1 to check why the air lock was not running. When the coworker heard Employee #1 scream, the coworker went to see what had happened, and he found Employee #1 lying on the floor underneath the electrical cord. It was determined that the plug was damaged and shorted out causing the electrocution and death of Employee #1.
Keywords: FURNACE, OVEN, ELECTROCUTED, INDUSTRIAL TRUCK, ELECTRIC SHOCK
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 312000847 | Fatality | Electric Shock | Occupation not reported |
Translate