Inspection Detail
Inspection: 311822761 - Pri/Del-Jen A Services Jv
Inspection Information - Office: Jacksonville Area Office
Site Address:
Pri/Del-Jen A Services Jv
7285 Uss Yorktown, Nas Whiting Field
Milton, FL 32570
Mailing Address:
7189 Langley Street, Milton, FL 32570
Union Status: Union
SIC:8744
NAICS: 561210/Facilities Support Services
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 07/30/2009
Emphasis: S:Electrical
Case Closed: 11/23/2009
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 101357580 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 7 | 7 | ||||
Current Violations | 4 | 3 | 7 | |||
Initial Penalty | $21,975 | $0 | $0 | $0 | $0 | $21,975 |
Current Penalty | $13,750 | $0 | $0 | $0 | $0 | $13,750 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Other | 19100137 B02 VIII | 10/06/2009 | 10/26/2009 | $0 | $1,875 | $0 | I - Informal Settlement | ||
2. | 01002 | Other | 19100269 A02 II | 10/06/2009 | 10/26/2009 | $0 | $1,875 | $0 | I - Informal Settlement | ||
3. | 01003 | Serious | 19100269 A02 III | 10/06/2009 | 10/26/2009 | $1,875 | $1,875 | $0 | I - Informal Settlement | ||
4. | 01004 | Serious | 19100269 C01 | 10/06/2009 | 10/26/2009 | $1,875 | $1,875 | $0 | I - Informal Settlement | ||
5. | 01005 | Other | 19100269 J02 III | 10/06/2009 | 10/26/2009 | $0 | $1,875 | $0 | I - Informal Settlement | ||
6. | 01006 | Serious | 19100269 M03 II | 10/06/2009 | 10/26/2009 | $5,000 | $6,300 | $0 | I - Informal Settlement | ||
7. | 01007 | Serious | 19100269 M03 V | 10/06/2009 | 10/26/2009 | $5,000 | $6,300 | $0 | I - Informal Settlement |
Investigation Summary
Employee #1 and a coworker were to install a new capacitor in a capacitor bank. Both employees were high voltage electricians. They did not conduct a job briefing prior to beginning this work. The power to the capacitor bank had not been disconnected and tagged. Employee #1 and the coworker did not verify that the capacitor bank and its related equipment were deenergized. When Employee #1 was connecting the wire from the oil switch to the fuse on the capacitor, he received an electrical shock, and went into cardiac arrest. Employee #1 was taken to a local hospital, and died.
Keywords: FUSE, ELECTRIC SWITCH, ELECTRICIAN, CAPACITOR, LOCKOUT, CARDIAC ARREST, ELEC CIRC PART--MISC, ELECTRIC SHOCK, TAG
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 311822761 | Fatality | Electric Shock | Supervisors; electricians & power transm. install. |