Inspection: 311817183 - Talquin Electric Cooperative, Inc.

Inspection Information - Office: Jacksonville Area Office

 

Inspection Nr: 311817183
Report ID: 0419700
Date Opened: 08/25/2008

Site Address:
Talquin Electric Cooperative, Inc.
431 Sawdust Road
Quincy, FL 32351

Mailing Address:
P.O. Box 1679, Quincy, FL 32353

Union Status: Union

SIC:4911

NAICS: 221122/Electric Power Distribution


Inspection Type: Accident

Scope: Complete

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 10/28/2008

Emphasis: L:Ohpwrlne, S:Electrical

Case Closed: 06/23/2009


Related Activity
Type Activity Nr Safety Health
Accident 101357010
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $6,000 $0 $0 $0 $0 $6,000
Current Penalty $4,500 $0 $0 $0 $0 $4,500
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100132 A 12/17/2008 01/14/2009 $500 $1,100 $0 I - Informal Settlement  
2. 01002A Serious 19100269 M03 II 12/17/2008 01/14/2009 $4,000 $4,900 $0 I - Informal Settlement  
3. 01002B Serious 19100269 M03 VI 12/17/2008 01/14/2009 $0 $0 $0 I - Informal Settlement  
4. 01002C Serious 19100335 A01 I 12/17/2008 01/14/2009 $0 $0 $0 I - Informal Settlement  
5. 01002D Serious 19100335 A02 I 12/17/2008 01/14/2009 $0 $0 $0 I - Informal Settlement Citation has been deleted.

Investigation Summary

Investigation Nr: 201353687
Event: 08/22/2008
Utility Worker Is Electrocuted by Overhead Power Line

On August 22, 2008 a lineman and a coworker were repairing a downed overhead power line during Tropical Storm Fay. A pine tree had been blown onto a single-phase 7,200-volt overhead power lines and the neutral-phase line, breaking the two lines between utility poles Number 5 and Number 6. Their job was to remove the pine tree from the road, and to reconnect the two lines. While the coworker used a chain saw to cut the pine tree into smaller pieces, the lineman elevated himself in an aerial bucket of their utility truck to the top of utility pole Number 5. The lineman told the coworker that he was going to check to determine if the line was energized. The coworker heard the lineman yell and saw him being electrocuted. The two workers did not deenergize the lines prior to working on them, and they did not install protective grounds on the lines. In addition, the lineman did not wear his rubberized insulated gloves.

Keywords: OVERHEAD POWER LINE, POWER LINE WORKER, GLOVE, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 311817183 Fatality Electric Shock Supervisors; electricians & power transm. install.
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.