Inspection Detail
Inspection: 311816474 - Pinnacle Constructors, Llc
Inspection Information - Office: Jacksonville Area Office
Site Address:
Pinnacle Constructors, Llc
1008 W. International Speedway Blvd.
Daytona Beach, FL 32114
Mailing Address:
2517 Bayview Drive, Fort Lauderdale, FL 33305
Union Status: NonUnion
SIC:1542
NAICS: 236220/Commercial and Institutional Building Construction
Inspection Type: Unprog Rel
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 06/13/2008
Emphasis: L:Fall, S:Commercial Constr, S:Fall From Height
Case Closed: 09/30/2008
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 101356889 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 2 | 1 | 3 | |||
Current Violations | 2 | 1 | 3 | |||
Initial Penalty | $3,000 | $0 | $0 | $0 | $0 | $3,000 |
Current Penalty | $1,800 | $0 | $0 | $0 | $0 | $1,800 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 19260501 B01 | 08/05/2008 | 08/12/2008 | $900 | $1,500 | $0 | I - Informal Settlement | ||
2. | 01002 | Serious | 19260501 B04 I | 08/05/2008 | 08/12/2008 | $900 | $1,500 | $0 | I - Informal Settlement | ||
3. | 02001 | Other | 19260503 A01 | 08/05/2008 | 08/22/2008 | $0 | $0 | $0 | I - Informal Settlement |
Investigation Summary
On May 21, 2008, Employee #1 was with a crew installing a steel security grate inside the duct system of a 10-ton Trane air conditioning system (Model Number THC120A4RGAOW2B, Serial Number 8044100711L) that was located on a roof. As he crawled into the duct to weld the grate into place, the back of his head contacted an energized heat strip on the air conditioning unit coil. Employee #1 was electrocuted. The electrical power to the air conditioning unit had not been deenergized and locked or tagged out.
Keywords: HEAD, VENTILATION, ELECTROCUTED, WELDER, LOCKOUT, DUCT, GRATING, INSTALLING, ROOF
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 311816474 | Occupation not reported |