Inspection Detail
Inspection: 311815476 - The Titan Electric Group, Inc.
Inspection Information - Office: Jacksonville Area Office
Site Address:
The Titan Electric Group, Inc.
819 Townsend Blvd
Jacksonville, FL 32211
Mailing Address:
2730-7 Clydo Road, Jacksonville, FL 32207
Union Status: NonUnion
SIC:1731
NAICS: 238210/Electrical Contractors
Inspection Type: Accident
Scope: Complete
Advanced Notice: Y
Ownership: Private
Safety/Health: Safety
Close Conference: 08/05/2008
Emphasis: S:Commercial Constr, S:Electrical
Case Closed: 12/10/2008
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 101356871 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 4 | 1 | 5 | |||
Current Violations | 4 | 1 | 5 | |||
Initial Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
Current Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 19260301 A | 11/12/2008 | 11/24/2008 | $0 | $0 | $0 | - | ||
2. | 01002A | Serious | 19260405 A01 I | 11/12/2008 | 11/17/2008 | $0 | $0 | $0 | - | ||
3. | 01002B | Serious | 19260416 A01 | 11/12/2008 | 11/17/2008 | $0 | $0 | $0 | - | ||
4. | 01003 | Serious | 19260417 B | 11/12/2008 | 11/20/2008 | $0 | $0 | $0 | - | ||
5. | 01004 | Serious | 19261053 B13 | 11/12/2008 | 11/17/2008 | $0 | $0 | $0 | - | ||
6. | 02001A | Other | 19040029 A | 11/12/2008 | 11/17/2008 | $0 | $0 | $0 | - | ||
7. | 02001B | Other | 19040029 B01 | 11/12/2008 | 12/09/2008 | $0 | $0 | $0 | - | ||
8. | 02001C | Other | 19040032 A02 | 11/12/2008 | 11/24/2008 | $0 | $0 | $0 | - |
Investigation Summary
On May 15, 2008, Employee #1 and Employee #2 of the Titan Electric Group, Inc., were helping to renovate a building by installing new electrical wiring. At the time of the accident, Employee #1 was in the attic area of the building. His coworker had informed him that one of the metal conduits was loose, and it was energizing the other conduits in the area. Employee #1 entered the attic area with a Greenlee GT-11 Voltage Detector to identify any energized conduits or wires. They did not disconnect the electrical sources. Employee #1 also had non-insulated tools (a Klein screwdriver and a Klein 9- inch side cutter), and he was wearing Klein Journeyman electrical gloves, which did not cover two of his fingers and his thumb of each hand. As he was crawling in the limited attic space, his chest and upper extremities made contact with an energized conduit or wire, and he was electrocuted by approximately 120 to 160 volts. Employee died as a result of the electrocution.
Keywords: ELEC INSULATION, ELEC PROTECT EQUIP, ELECTRICAL, GLOVE, ELECTROCUTED, ELEC EQUIPMENT--MISC
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 311815476 | Fatality | Electric Shock | Occupation not reported |