Powered by GoogleTranslate

Inspection Detail

Inspection: 311390835 - Aee - Tecnica De Aguadilla

Inspection Information - Office: Pr-E-Mayaguez 0257240

 

Inspection Nr: 311390835
Report ID: 0257240
Date Opened: 03/15/2010

Site Address:
Aee - Tecnica De Aguadilla
Carr 112 Km 17.1 Bo Rocha
Moca, PR 00676

Mailing Address:
Po Box 364267, San Juan, PR 00936

Union Status: Union

SIC:4911

NAICS: 221122/Electric Power Distribution


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: StateGovt

Safety/Health: Safety

Close Conference: 03/15/2010

Emphasis:

Case Closed: 01/10/2013


Related Activity
Type Activity Nr Safety Health
Accident 101250306
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 5 1 6
Current Violations 1 1
Initial Penalty $35,000 $70,000 $0 $0 $0 $105,000
Current Penalty $3,000 $0 $0 $0 $0 $3,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 6000B 09/13/2010 09/17/2010 $7,000 $7,000 $0 09/22/2010 F - Formal Settlement Citation has been deleted.
2. 01002 Serious 19100269 A02 I 09/13/2010 09/26/2010 $7,000 $7,000 $0 09/22/2010 F - Formal Settlement Citation has been deleted.
3. 01003 Serious 19100269 A03 09/13/2010 09/17/2010 $7,000 $7,000 $0 09/22/2010 F - Formal Settlement Citation has been deleted.
4. 01004 Serious 19100269 C 09/13/2010 09/17/2010 $7,000 $7,000 $0 09/22/2010 F - Formal Settlement Citation has been deleted.
5. 01005 Serious 19100269 O02 I 09/13/2010 09/17/2010 $3,000 $7,000 $0 09/22/2010 F - Formal Settlement  
6. 02001 Willful 19100269 M02 I 09/13/2010 09/17/2010 $70,000 $70,000 $0 09/22/2010 F - Formal Settlement Citation has been deleted.

Investigation Summary

Investigation Nr: 201250305
Event: 03/14/2010
Employee Grabs an Energized Line, Is Electrouted and Dies

At approximately 2:30 p.m. in March 14, 2010, Employee #1 was repairing damage in a 4,160 V circuit power line. In the process, the employee cut a bridge, a small connection line which joins one part of the power line before the brass pole and the power line after the bras pole. To complete this bridge, the line before the post would be deenergized and the line after the post would be energized. The supervisor had not deenergized the first section of the line, and had not communicated that to the employee. When the employee climbed to connect both cables of the bridge, he grabbed the part of the line which was live and was electrocuted. Employee # 1 died a few minutes later.

Keywords: ELECTROCUTED, ELECTRICAL WORK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 311390835 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close