Inspection Detail
Inspection: 310990106 - Ashley Paulk, Inc. Dba Valdosta Electric Co.,Inc.
Inspection Information - Office: Savannah Area Office
Site Address:
Ashley Paulk, Inc. Dba Valdosta Electric Co.,Inc.
2000 Potato Roll Lane
Valdosta, GA 31601
Mailing Address:
3485 Bemiss Rd., Valdosta, GA 31605
Union Status: NonUnion
SIC:1731
NAICS: 238210/Electrical Contractors
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 08/07/2008
Emphasis: S:Commercial Constr, S:Electrical
Case Closed: 03/06/2009
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 100904069 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 4 | 4 | ||||
| Current Violations | 4 | 4 | ||||
| Initial Penalty | $12,800 | $0 | $0 | $0 | $0 | $12,800 |
| Current Penalty | $12,050 | $0 | $0 | $0 | $0 | $12,050 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19260021 B02 | 01/16/2009 | 02/05/2009 | $1,125 | $1,500 | $0 | I - Informal Settlement | ||
| 2. | 01002 | Serious | 19260416 A01 | 01/16/2009 | 01/22/2009 | $4,900 | $4,900 | $0 | - | ||
| 3. | 01003 | Serious | 19260416 A03 | 01/16/2009 | 01/22/2009 | $4,900 | $4,900 | $0 | - | ||
| 4. | 01004 | Serious | 19260417 C | 01/16/2009 | 01/22/2009 | $1,125 | $1,500 | $0 | I - Informal Settlement |
Investigation Summary
At approximately 10:00 a.m. on August 4, 2008, Employee #1 was an electrician. He and his helper were working at a construction site. They were in the mezzanine deck mechanical room and were installing new wiring from one of the bus plugs that was attached to the busway duct system to a breaker in one of the pan system control cabinets. Employee #1 was attaching the load-side wires from the bus plug to a 400 amp breaker located in the pan system control cabinet. The helper had difficulty lining up the screw holes to secure the cover for the bus plug breaker. He engaged the bus plug breaker to the "on" position, apparently at the same time that Employee #1 was tightening the load-side lugs inside the pan system control cabinet. Employee #1 was electrocuted.
Keywords: SHOCK, ELECTRICIAN, ELECTROCUTED, BUSBAR, ELECTRIC SHOCK, ELECTRICAL CABINET
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 310990106 | Fatality | Electric Shock | Supervisors; electricians & power transm. install. |
Translate