Inspection: 310816665 - San Diego Gas & Electric

Inspection Information - Office: San Diego District Office

 

Inspection Nr: 310816665
Report ID: 0950632
Date Opened: 05/18/2008

Site Address:
San Diego Gas & Electric
8290 Miramar Rd
San Diego, CA 92126

Mailing Address:
101 Ash St, San Diego, CA 92101

Union Status: Union

SIC:4925

NAICS: 221210/Natural Gas Distribution


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 11/17/2008

Emphasis:

Case Closed: 08/30/2011


Related Activity
Type Activity Nr Safety Health
Accident 362411381
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 8 8
Current Violations 5 3 8
Initial Penalty $103,045 $0 $0 $0 $0 $103,045
Current Penalty $76,270 $0 $0 $2,760 $0 $79,030
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 2940 C 11/17/2008 12/19/2008 $850 $7,650 $0 12/09/2008 J - ALJ Decision  
2. 02001 Other 29400002 A 11/17/2008 12/19/2008 $1,060 $11,475 $0 12/09/2008 J - ALJ Decision  
3. 03001 Serious 29400009 11/17/2008 12/19/2008 $27,000 $27,000 $0 12/09/2008 J - ALJ Decision  
4. 04001 Serious 2943 G01 B 11/17/2008 12/19/2008 $9,560 $9,560 $0 12/09/2008 J - ALJ Decision  
5. 05001 Serious 2943 G01 D 11/17/2008 12/19/2008 $9,560 $9,560 $0 12/09/2008 J - ALJ Decision  
6. 06001 Serious 2943 G01 G 11/17/2008 12/19/2008 $22,500 $22,500 $0 12/09/2008 J - ALJ Decision  
7. 07001 Other 3203 A07 D 11/17/2008 12/19/2008 $850 $7,650 $0 12/09/2008 J - ALJ Decision  
8. 08001 Serious 3203 A07 F 11/17/2008 12/19/2008 $7,650 $7,650 $0 -  

Investigation Summary

Investigation Nr: 201072451
Event: 05/18/2008
Employee Suffers Electrocution from Terminator, Later Dies

On May 18, 2008, Employee #1 was the working foreman of a gas crew assigned to assist an electrical repair crew for an unplanned outage of a high-voltage electrical line identified as Circuit 227. The electrical repair required that the terminator, the terminator cabinet, and the underground conduits containing high-voltage cables between the terminator and a fuse box to be replaced. A gas crew was called in to assist the electrical crew with traffic control and digging to expose the conduits to be replaced. Circuit 227 was opened and deenergized between Switch 227-44 and the Miramar Substation so that the work could be performed. At approximately 12:57 a.m., Employee #1 was observing a coworker digging and was moving a halogen light on a metal tripod from the top of a soil spoils pile onto level ground nearby. As Employee #1 was moving the tripod, his right thigh made contact with a primary cable on the terminator, causing an electrical arc. Employee #1 was exposed to approximately 6,930 volts of electricity generated from back feed, thrown backwards approximately two feet, and landed on the ground. Coworkers attempted CPR until emergency crews arrived. Employee #1 was taken to Scripps Memorial Hospital in La Jolla, where he was pronounced dead. The accident was reported at 9:15 a.m. and the employer did fulfill the 8-hour reporting requirement.

Keywords: ELECTRIC ARC, OVERHEAD POWER LINE, CPR, ELECTRIC CABLE, ELECTROCUTED, NATURAL GAS, THIGH, TRAFFIC CONTROL, GAS, ELEC UTILITY WORK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 310816665 Fatality Electric Shock Welders and cutters
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close