Inspection Detail
Inspection: 310803481 - Jodan Contracting Inc.
Inspection Information - Office: Peoria Area Office
Site Address:
Jodan Contracting Inc.
554 N. 1800 East Rd.
Goodwine, IL 60939
Mailing Address:
746 N. 1470 E. Rd., Cissna Park, IL 60924
Union Status: NonUnion
SIC:1731
NAICS: 238210/Electrical Contractors
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 10/10/2008
Emphasis: S:Commercial Constr, S:Electrical
Case Closed: 03/20/2009
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 100273366 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 3 | 1 | 4 | |||
| Current Violations | 3 | 1 | 4 | |||
| Initial Penalty | $4,500 | $0 | $0 | $1,500 | $0 | $6,000 |
| Current Penalty | $2,700 | $0 | $0 | $900 | $0 | $3,600 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001A | Serious | 19260020 B01 | 10/17/2008 | 11/13/2008 | $900 | $1,500 | $0 | I - Informal Settlement | ||
| 2. | 01001B | Serious | 19260021 B02 | 10/17/2008 | 11/13/2008 | $0 | $0 | $0 | I - Informal Settlement | ||
| 3. | 01002 | Serious | 19260405 D | 10/17/2008 | 10/23/2008 | $900 | $1,500 | $0 | I - Informal Settlement | ||
| 4. | 01003 | Serious | 19260416 A01 | 10/17/2008 | 11/13/2008 | $900 | $1,500 | $0 | I - Informal Settlement | ||
| 5. | 02001 | Other | 19040039 A | 10/17/2008 | 10/23/2008 | $900 | $1,500 | $0 | I - Informal Settlement |
Investigation Summary
At approximately 4:45 p.m., on September 16, 2008, two employees of Jodan Contracting, Inc., were running electrical wire and conduit as part of a grain dryer installation at Goodwine Co-op Grain Company, located in Goodwine, Illinois. Employee #1 was the qualified person and was providing on-the-job training for Employee #2. The employees had some extra time at the end of the day and Employee #1 instructed Employee #2 in the installation of a cold bonding wire at the base of an energized 480-volt panel box. Employee #1 gave Employee #2 verbal instructions and demonstrated to Employee #2 how to install the ground. The panel was not deenergized prior to installing the ground. Employee #1 told Employee #2 to install the wire and then to come out of the power room. Employee #1 stepped outside and waited for approximately 5-10 minutes. Employee #1 returned to the power room when Employee #2 didn't come out and Employee #1 found Employee #2 unresponsive with his head in the bottom of the panel box. Emergency services responded and transported Employee #2 to the hospital where he was pronounced dead due to electrocution.
Keywords: PANEL, ELECTRICIAN, ELECTROCUTED, CONSTRUCTION, ELECTRICAL WORK, ELEC CIRC PART--MISC, ELECTRIC CONDUCTOR
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 310803481 | Fatality | Electric Shock | Electricians' apprentices |