Powered by GoogleTranslate

Inspection Detail

Inspection: 310488382 - Sweetener Products - Vernon Warehouse

Inspection Information - Office: Long Beach District Office

 

Inspection Nr: 310488382
Report ID: 0950642
Date Opened: 08/01/2007

Site Address:
Sweetener Products - Vernon Warehouse
2322 East 37th Street
Vernon, CA 90058

Mailing Address:
2050 East 38th Street, Vernon, CA 90058

Union Status: NonUnion

SIC:4212

NAICS: 484220/ Specialized Freight (except Used Goods) Trucking, Local


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 09/21/2007

Emphasis:

Case Closed: 01/13/2009


Related Activity
Type Activity Nr Safety Health
Accident 102470614
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 3 4
Current Violations 4 4
Initial Penalty $20,250 $0 $0 $1,295 $0 $21,545
Current Penalty $0 $0 $0 $1,700 $0 $1,700
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 3314 H 09/21/2007 10/24/2007 $0 $325 $0 10/17/2007 F - Formal Settlement  
2. 01002 Other 23400022 A 09/21/2007 10/24/2007 $250 $485 $0 10/17/2007 F - Formal Settlement  
3. 01003 Other 3314 G 09/21/2007 10/24/2007 $250 $485 $0 10/17/2007 F - Formal Settlement  
4. 02001 Other 23200002 A 09/21/2007 10/03/2007 $1,200 $20,250 $0 10/17/2007 F - Formal Settlement  

Investigation Summary

Investigation Nr: 202453775
Event: 07/23/2007
Employee Is Burned by Arc Flash

At approximately 9:00 p.m. on July 23, 2007, Employee #1 was an electrician with Sweetener Products Co., a company that warehoused and distributed sugar and sugar syrups to industry. He was working alone on an electrical panel in the electrical penthouse of the maintenance building. An additional branch circuit was being run from the 480V, 3000A main panel of the maintenance building which required the installation of a 400A circuit breaker. While the panel was still energized, Employee #1 removed the front access cover and sat down near the corner of the panel in order to bolt the circuit breaker onto the bus bar brackets. The mounting holes of the breaker were not aligned with the threaded bus bar bracket holes. Employee #1 used a steel ball peen hammer with a wooden handle to tap the lowest bus bar bracket upwards in an attempt to align the mounting holes. He caused an arc flash that burned his face, arms and lower left leg. He was hospitalized for treatment of his burns.

Keywords: BURN, ELECTRIC ARC, ELECTRICIAN, ELECTRICAL CABINET, ARM, HAND TOOL, FACE, LEG

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 310488382 Hospitalized injury Burn/Scald(Heat) Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.