Inspection Detail
Inspection: 310479985 - Pike Electric, Inc.
Inspection Information - Office: Columbus Area Office
Site Address:
Pike Electric, Inc.
13675 Sand Rock Road
Glenford, OH 43739
Mailing Address:
P.O. Box 868, Mount Airy, NC 27030
Union Status: NonUnion
SIC:4911
NAICS: 221122/Electric Power Distribution
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 09/19/2007
Emphasis: S:Electrical, S:Hwy Street Bridge Constr
Case Closed: 02/03/2009
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 100752823 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 2 | 2 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $14,000 | $0 | $0 | $0 | $0 | $14,000 |
| Current Penalty | $10,000 | $0 | $0 | $0 | $0 | $10,000 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19100269 Q01 II | 09/19/2007 | 09/29/2007 | $10,000 | $7,000 | $0 | I - Informal Settlement | ||
| 2. | 01002 | Serious | 19100269 Q01 III | 09/19/2007 | 09/29/2007 | $7,000 | $7,000 | $0 | I - Informal Settlement | Citation has been deleted. |
Investigation Summary
At approximately 11:15 a.m. on July 9, 2007, an employee, working with a four man crew, had installed a new pole and moved the lines to the new pole prior to the accident. The primary line had been covered with insulated line hoses and blankets. The crew positioned the equipment to remove the old pole. A choker was attached to the pole to lift the pole and the pole grabber on the line truck was hooked around the pole. The pole was then lifted approximately 12 to 18 inches up. The foreman then instructed the employee, a groundman, to cut off the pole with a chain saw. When the cut was made, the bottom of the pole kicked out toward the road, where the employee was standing. The employee tried to use his hands to push the pole back from hitting him. When the pole kicked out, the top of the pole contacted the energized primary line. The employee, who was not wearing required PPE, rubber gloves, was electrocuted.
Keywords: OVERHEAD POWER LINE, PPE, ELECTROCUTED
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 310479985 | Fatality | Electric Shock | Electrical power installers and repairers |
Translate