Powered by GoogleTranslate

Inspection Detail

Inspection: 310223698 - Djw Enterpises, Inc. Dba Winningham Electric

Inspection Information - Office: Lubbock Area Office

 

Inspection Nr: 310223698
Report ID: 0627400
Date Opened: 08/16/2006

Site Address:
Djw Enterpises, Inc. Dba Winningham Electric
1900 N Clack
Abilene, TX 79603

Mailing Address:
1208 State Hwy 29, Llano, TX 78643

Union Status: NonUnion

SIC:1731

NAICS: 238210/Electrical Contractors


Inspection Type: Accident

Scope: Complete

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 01/21/2007

Emphasis:

Case Closed: 06/04/2007


Related Activity
Type Activity Nr Safety Health
Accident 100813120
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations 3 3
Initial Penalty $4,500 $0 $0 $0 $0 $4,500
Current Penalty $4,500 $0 $0 $0 $0 $4,500
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100333 A01 02/02/2007 02/07/2007 $1,500 $1,500 $0 -  
2. 01002 Serious 19100335 A01 I 02/02/2007 02/07/2007 $1,500 $1,500 $0 -  
3. 01003A Serious 19100335 A02 II 02/02/2007 02/07/2007 $1,500 $1,500 $0 -  
4. 01003B Serious 19100335 B01 02/02/2007 02/07/2007 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 200812196
Event: 08/06/2006
One employee killed, one coworker injured in arc flash

On August 6, 2006, Employee #1, a certified electrician, and a helper, were repairing an energized three-phase, 480-volt AC circuit. When the final circuit conductors were being connected at the control panel, the ground wire was accidentally shorted directly to the phase terminals, creating an arc fault and flash. The blast of released energy struck Employee #1 full force; he suffered serious injuries that eventually resulted in his death. The coworker was knocked down and suffered contusions and abrasions, along with a headache and a temporary loss of hearin. Subsequent investigation determined that the circuit was energized unnecessarily, no form of personal protective equipment was being used, and no insulating materials/shields or devices were in place to protect from such accidental contacts. The panel was not appropriately marked for arc fault/flash hazards, and no form of warning, such as barriers, signs or symnols) were in place.

Keywords: ELECTRIC ARC, INSULATED TOOL, WORK RULES, ELECTROCUTED, CONSTRUCTION, HEARING LOSS, ELEC CIRC PART--MISC, ELECTRICAL FAULT, WARNING SIGN

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 310223698 Fatality Other Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close