Powered by GoogleTranslate

Inspection Detail

Inspection: 310197660 - Bay City Electrical Works, Inc.

Inspection Information - Office: Van Nuys District Office

 

Inspection Nr: 310197660
Report ID: 0950643
Date Opened: 06/13/2007

Site Address:
Bay City Electrical Works, Inc.
18700 Burbank Blvd.
Tarzana, CA 92040

Mailing Address:
12208 Industry Rd., Lakeside, CA 92040

Union Status: NonUnion

SIC:1731

NAICS: 238210/Electrical Contractors


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/25/2007

Emphasis:

Case Closed: 08/12/2008


Related Activity
Type Activity Nr Safety Health
Accident 101119287
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $14,400 $0 $0 $0 $0 $14,400
Current Penalty $0 $0 $0 $550 $0 $550
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 23200002 A 12/05/2007 12/15/2007 $550 $14,400 $0 01/31/2008 F - Formal Settlement  

Investigation Summary

Investigation Nr: 202465266
Event: 06/05/2007
EMPLOYEE burned by electrical arc from circuit breaker panel

At approximately 2:45 p.m. on June 5, 2007, Employee #1, a journeyman electrician, was troubleshooting and performing diagnostics to determine the source of intermittent power failures at a senior living facility in Tarzana, CA. He had isolated the problem to a 480 volt circuit breaker in the electrical room. The circuit breaker is normally enclosed by a panel to protect against accidental contact. Employee #1 had removed his gloves when he noticed the surface as well as the side of the circuit breaker were hot to the touch. He was using a screwdriver to re-install the cover on the panel when it fell onto the exposed energized sections of the panel. This caused an electrical arc from phase-to-phase and produced an electrical flash. Employee #1 sustained serious burns and was transported to Grossman Burn Center, where he was hospitalized for seven days and underwent skin grafts. Employee #1 was working alone at the time of the incident. The employer was cited for a serious, accident-related violation of T8CCR 2320.2(a), for failing to use insulated tools in accordance with ASTM 1505-94.

Keywords: BURN, ELECTRIC ARC, REPAIR, ELECTRICAL, INSULATED TOOL, WORK RULES, CONSTRUCTION, ELECTRICAL WORK, ELECTRICAL CABINET

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 310197660 Hospitalized injury Burn/Scald(Heat) Misc. electrical & electronic equipment repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.