Powered by GoogleTranslate

Inspection Detail

Inspection: 310097811 - Jeffrey Smith Dba Zoecom

Inspection Information - Office: Foster City District Office

 

Inspection Nr: 310097811
Report ID: 0950613
Date Opened: 05/28/2010

Site Address:
Jeffrey Smith Dba Zoecom
10591 La Honda Road, Pole #59-1
La Honda, CA 94020

Mailing Address:
Po Box 370752, Montara, CA 94037

Union Status: NonUnion

SIC:1623

NAICS: 237130/Power and Communication Line and Related Structures Construction


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/09/2010

Planning Guide: Safety-Construction

Emphasis: S:Construction (Cship)

Case Closed: 04/16/2011


Related Activity
Type Activity Nr Safety Health
Accident 101134807
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations 1 1
Initial Penalty $22,680 $0 $0 $0 $0 $22,680
Current Penalty $5,400 $0 $0 $0 $0 $5,400
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 2946 A 06/15/2010 06/25/2010 $5,400 $10,800 $0 I - Informal Settlement  
2. 02001 Serious 2946 B02 06/15/2010 06/25/2010 $0 $1,080 $0 I - Informal Settlement Citation has been deleted.
3. 03001 Serious 8602 H 06/15/2010 06/25/2010 $0 $10,800 $0 I - Informal Settlement Citation has been deleted.

Investigation Summary

Investigation Nr: 201127560
Event: 05/10/2010
Electric Shock - Direct Contact with Overhead Line

An employee was working on a 7.6-meter-tall utility pole, installing a communication cable. The communications pole was between two utility poles supporting a 12-kilovolt overhead power line that was about 610 millimeters above the communications line. As he raised his right arm to pull out a cable strand, the employee contacted the power line. The employee received an electric shock and burns to his right shoulder and the back of his right hand. The employee's supervisor used an aerial lift to lower the injured employee. The injured employee was taken to the nearest fire department (about 15 minutes away), which transported him to a medical center via helicopter. He had surgery for his injuries and was hospitalized for 7 days. The employee and supervisor stated, after the accident, that they did not notice the overhead power line, which was sagging near the communications line.

Keywords: BURN, OVERHEAD POWER LINE, ELECTRICAL, TELECOM WORK, E TC, ELECTRIC SHOCK, SUSPENSION STRAND, UTILITY POLE, COMMUNICATION WORKER

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 310097811 Hospitalized injury Electric Shock Engineering technicians, n.e.c.
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.