Inspection: 309769453 - Dubak Electrical Maintenance Corp.

Inspection Information - Office: Naperville Area Office

 

Inspection Nr: 309769453
Report ID: 0521400
Date Opened: 11/13/2006

Site Address:
Dubak Electrical Maintenance Corp.
5 South 220 Frontenac Rd.
Naperville, IL 60563

Mailing Address:
417 South Bluff Ave., Lagrange, IL 60525

Union Status: NonUnion

SIC:1731

NAICS: 238210/Electrical Contractors


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 03/15/2007

Planning Guide: Safety-Construction

Emphasis: S:Electrical

Case Closed: 03/15/2007


Related Activity
Type Activity Nr Safety Health
Accident 100821669

Investigation Summary

Investigation Nr: 200823409
Event: 11/13/2006
Employee electrocuted by energized plug receptacle

On November 13, 2006, Employee #1 received a call on his cell phone from a coworker asking him to find the serial/order number of a 480-volt/three-phase attachment plug so that more attachment plugs could be ordered. Employee #1 found such a plug, possibly choosing it because it was in an idle machine and the only one not in production. Employee #1 accidentally placed the ground prong into the energized plug receptacle and grounded out, causing the third-phase fuse to blow. He was electrocuted. The wiring and the Chicago Pyle/National attachment plug were found to be very dilapidated and had not been inspected or maintained. Because of the configuration of the plug, any of the eight-prong male plugs could have been inadvertently placed in any of the female receptacles, energizing the metal casing. Because of Employee #1's medical condition and the fact that there were no electrical burns inside or outside his body, the coroner considered ruling the cause of death as natural causes/coronary disease. After continuity testing and destructive testing of the evidence, the cause of death was ruled to be electrocution.

Keywords: FUSE, ELECTRICAL, INADEQUATE MAINT, WORK RULES, ELECTROCUTED, CONSTRUCTION, ELECTRICAL WORK, ATTACHMENT PLUG, ELEC CIRC PART--MISC

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 309769453 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.