Inspection: 309717411 - Verizon North Inc.

Inspection Information - Office: Indiana Department Of Labor

 

Inspection Nr: 309717411
Report ID: 0551800
Date Opened: 07/06/2006

Site Address:
Verizon North Inc.
1434 Johnson Street
Elkhart, IN 46515

Mailing Address:
19845 Us Hwy 31 N, Westfield, IN 46074

Union Status: NonUnion

SIC:4813

NAICS: 517110/Wired Telecommunications Carriers


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/30/2006

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 01/23/2008


Related Activity
Type Activity Nr Safety Health
Accident 100990845
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations
Initial Penalty $10,000 $0 $0 $0 $0 $10,000
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100268 E 10/03/2006 10/06/2006 $5,000 $5,000 $0 11/02/2006 J - ALJ Decision Citation has been deleted.
2. 01002 Serious 19100268 F01 10/03/2006 10/30/2006 $5,000 $5,000 $0 11/02/2006 J - ALJ Decision Citation has been deleted.

Investigation Summary

Investigation Nr: 200995819
Event: 05/26/2006
Employee Is Electrocuted While Repairing Phone Service

On May 26, 2006, Employee #1 was working on the main frame, where there was trouble with a costumer's phone service. Employee was working alone and was electrocuted. The exact cause of the accident was unknown, but the cause of death was consistent with electrocution. The employee had an entry wound on his left hand and an exit wound on his right hand. Piece of equipment employee was allegedly working with was called a breakdown box, which was a small transformer. However, the equipment was missing its ground prong. The breakdown box had the ability of different amounts of voltage, 350, 500, and 700. There were two alligator clips one with blue insulation and the other was black. The blue cable had the insulation on the alligator clip missing, and appeared to have been ripped away. There was no PPE at the site of the accident, and the employee did not have any with him.

Keywords: ELEC INSULATION, PPE, ELECTROCUTED, TRANSFORMER, HAND

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 309717411 Fatality Electric Shock Telephone line installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.