Inspection Detail
Inspection: 309539021 - Globe Electric Service
Inspection Information - Office: Dallas Area Office
Site Address:
Globe Electric Service
2011 Drake Dr.
Richardson, TX 75081
Mailing Address:
11315 Jupiter Rd., Dallas, TX 75218
Union Status: NonUnion
SIC:1731
NAICS: 238210/Electrical Contractors
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 12/14/2006
Emphasis:
Case Closed: 10/17/2007
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 100783786 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 4 | 4 | ||||
| Current Violations | 4 | 4 | ||||
| Initial Penalty | $4,500 | $0 | $0 | $0 | $0 | $4,500 |
| Current Penalty | $1,500 | $0 | $0 | $0 | $0 | $1,500 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001A | Serious | 19100332 B01 | 12/15/2006 | 12/20/2006 | $500 | $1,500 | $0 | 01/15/2007 | F - Formal Settlement | |
| 2. | 01001B | Serious | 19260021 B02 | 12/15/2006 | 12/20/2006 | $0 | $0 | $0 | 01/15/2007 | F - Formal Settlement | |
| 3. | 01002A | Serious | 19100333 A01 | 12/15/2006 | 12/20/2007 | $500 | $1,500 | $0 | 01/15/2007 | F - Formal Settlement | |
| 4. | 01002B | Serious | 19100333 A02 | 12/15/2006 | 12/20/2006 | $0 | $0 | $0 | 01/15/2007 | F - Formal Settlement | |
| 5. | 01002C | Serious | 19100335 A01 I | 12/15/2006 | 12/20/2006 | $0 | $0 | $0 | 01/15/2007 | F - Formal Settlement | |
| 6. | 01003A | Serious | 19100333 B02 | 12/15/2006 | 12/20/2006 | $250 | $750 | $0 | 01/15/2007 | F - Formal Settlement | |
| 7. | 01003B | Serious | 19260417 B | 12/15/2006 | 12/20/2006 | $0 | $0 | $0 | 01/15/2007 | F - Formal Settlement | |
| 8. | 01004A | Serious | 19100333 B02 I | 12/15/2006 | 12/20/2006 | $250 | $750 | $0 | 01/15/2007 | F - Formal Settlement | |
| 9. | 01004B | Serious | 19260020 B01 | 12/15/2006 | 12/20/2006 | $0 | $0 | $0 | 01/15/2007 | F - Formal Settlement |
Investigation Summary
On July 1, 2006, Employee #1, of Globe Electric Service, was in the attic of an existing home, working on an energized multi-conductor branch circuit to repair a malfunctioning 120-volt receptacle in the kitchen. The 20-amp branch circuit originated from a single panelboard in the master bedroom walk-in closet. In Employee #1's immediate work area was a blue PVC single gang nail-on box that did not have a cover. Three 12/2 type NM-B cables--a cable from a service panel, a cable to an electrical outlet, and a cable to a ceiling fan in the kitchen--entered the box and were spliced together. None of the splices were made with wire nuts and the bare conductors were exposed. The Type NM-B cable to the ceiling fan was pulled from the box, and the bare conductors for it were also exposed. As he was working, Employee #1 apparently contacted one or more bare conductors and was electrocuted. He had not been protected from contacting the energized equipment, parts, or circuits by guarding, isolation, or insulation. Employee #1 was not wearing, nor had he been provided, voltage-rated rubber gloves. No safety-related work practices had been developed and implemented for the work he was doing.
Keywords: ELEC PROTECT EQUIP, REPAIR, ELECTRICAL, WORK RULES, ELECTROCUTED, STRUCK AGAINST, CONSTRUCTION, ELEC CIRC PART--MISC, ELECTRICAL SPLICE, UNTRAINED
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 309539021 | Fatality | Electric Shock | Electricians |
Translate