Inspection: 309443521 - Paulding-Putnam Electric Cooperative

Inspection Information - Office: Toledo Area Office

 

Inspection Nr: 309443521
Report ID: 0524700
Date Opened: 09/12/2006

Site Address:
Paulding-Putnam Electric Cooperative
6215 Road 205
Oakwood, OH 45873

Mailing Address:
910 N. Williams, Paulding, OH 45879

Union Status: NonUnion

SIC:4911

NAICS: 221122/Electric Power Distribution


Inspection Type: Referral

Scope: Partial

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 09/12/2006

Emphasis:

Case Closed: 12/05/2006


Related Activity
Type Activity Nr Safety Health
Referral 202098968 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 1 4
Current Violations 2 2
Initial Penalty $7,500 $0 $0 $0 $0 $7,500
Current Penalty $0 $0 $0 $2,500 $0 $2,500
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100269 P04 III 10/04/2006 10/10/2006 $2,500 $2,500 $0 I - Informal Settlement Citation has been deleted.
2. 01002 Serious 19100269 Q01 II 10/04/2006 10/10/2006 $2,500 $2,500 $0 I - Informal Settlement Citation has been deleted.
3. 01003 Other 19100269 Q01 III 10/04/2006 10/10/2006 $2,500 $2,500 $0 I - Informal Settlement  
4. 02001 Other 19100137 B02 VIII 10/04/2006 10/10/2006 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 202087714
Event: 09/07/2006
Electric Shock - Contact with Overhead Line thru Pole

A power line crew was replacing a utility pole and reconnecting service to a remodeled house. One crew member was operating an Altec D-842 digger-derrick, and the other two crew members were guiding the pole into the ground. One of these two workers was wearing rubber insulated gloves with leather protectors, but the other was wearing only leather gloves. The pole contacted a 7,200-volt, single-phase, overhead power line. (The pole had a copper ground line attached to its entire length, and it contacted the power line.) The worker who was wearing only leather gloves received an electric shock, with entry and exit wounds on his right hand and right foot. He was hospitalized with third-degree burns to his right arm, hand, and foot and a fractured shoulder. The morning of the accident was sunny, and light dew covered the ground.

Keywords: BURN, DIGGER-DERRICK, ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK, UTILITY POLE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 309443521 Hospitalized injury Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.