Inspection Detail
Inspection: 309184554 - Northern Kentucky Electric Service, Inc.
Inspection Information - Office: Columbus Area Office
Site Address:
Northern Kentucky Electric Service, Inc.
475 Metro Place North
Dublin, OH 43017
Mailing Address:
P.O. Box 380, Alexandria, KY 41001
Union Status: NonUnion
SIC:1731
NAICS: 238210/Electrical Contractors
Inspection Type: Referral
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 06/22/2006
Emphasis:
Case Closed: 11/22/2006
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Referral | 200752160 | Yes |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 4 | 4 | ||||
| Current Violations | 4 | 4 | ||||
| Initial Penalty | $10,000 | $0 | $0 | $0 | $0 | $10,000 |
| Current Penalty | $5,000 | $0 | $0 | $0 | $0 | $5,000 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19100147 C06 I | 08/25/2006 | 10/20/2006 | $1,250 | $2,500 | $0 | I - Informal Settlement | ||
| 2. | 01002 | Serious | 19100332 B01 | 08/25/2006 | 10/05/2006 | $1,250 | $2,500 | $0 | I - Informal Settlement | ||
| 3. | 01003 | Serious | 19100335 A01 I | 08/25/2006 | 09/12/2006 | $1,250 | $2,500 | $0 | I - Informal Settlement | ||
| 4. | 01004 | Serious | 19100335 A02 I | 08/25/2006 | 09/12/2006 | $1,250 | $2,500 | $0 | I - Informal Settlement |
Investigation Summary
At approximately 1:40 p.m. on or about June 20, 2006, Employee #1, of Northern Kentucky Electric Service, Inc., was identifying and repairing switch problems on an HVAC pump. The switch was a part of the 1,600-amp master control panel for an occupied commercial building. The line side was energized and the load side was off; the current was 480 volts, phase-to-phase, and 270 volts, phase-to-ground. Employee #1 was using an uninsulated tool to tighten amps and receivers when an arc flash occurred. He sustained second- and third-degree burns to his face, right hand, and right arm, for which he was hospitalized.
Keywords: BURN, ELEC PROTECT EQUIP, ELECTRIC ARC, ELECTRICAL, ELECTRIC SWITCH, INSULATED TOOL, WORK RULES, CONSTRUCTION, ELEC CIRC PART--MISC, FACE
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 309184554 | Hospitalized injury | Burn/Scald(Heat) | Electricians |
Translate