Powered by GoogleTranslate

Inspection Detail

Inspection: 309172716 - Great Salt Lake Minerals & Chemicals

Inspection Information - Office: Utah Division Of Occupational Safety And Health

 

Inspection Nr: 309172716
Report ID: 0854910
Date Opened: 09/29/2006

Site Address:
Great Salt Lake Minerals & Chemicals
765 North 10500 West
North Ogden, UT 84402

Mailing Address:
765 W 10500 N, Ogden, UT 84402

Union Status: NonUnion

SIC:1481

NAICS: 213115/Support Activities for Nonmetallic Minerals (except Fuels)


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 01/12/2007

Planning Guide: Safety-Manufacturing

Emphasis: S:Amputations, S:General Industry, S:Immigrant, S:Small Business

Case Closed: 03/28/2007


Related Activity
Type Activity Nr Safety Health
Accident 101564243
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $8,000 $0 $0 $0 $0 $8,000
Current Penalty $2,800 $0 $0 $0 $0 $2,800
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 10005 D03 02/07/2007 02/12/2007 $1,400 $4,000 $0 I - Informal Settlement  
2. 01002A Serious 10005 D04 02/07/2007 02/15/2007 $1,400 $4,000 $0 I - Informal Settlement  
3. 01002B Serious 19100147 C07 IIIC 02/07/2007 02/15/2007 $0 $0 $0 -  
4. 01002C Serious 19100147 E02 I 02/07/2007 02/13/2007 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 201561719
Event: 09/29/2006
Employee Is Electrocuted after Repairing Sump Motor

At approximately 12:30 a.m., on or near September 29, 2006, Employee #1, a technical mechanic, and an electrical mechanic were about to replace a sump motor. After the electrical mechanic locked out the sump motor circuit breaker, located in the motor control room ("MCC-006") of the Wet Process Building, he set the outside sump switch to the "off" position and wired the new motor. Prior to returning the pump back to the sump, the employees attached a 3-inch diameter, right-angle pipe to the pump. The electrical mechanic returned to the MCC room to check on the leads to the motor and called the lead electrician to confirm that the readings were acceptable. After he was given clearance, the electrical mechanic removed his lock and energized the circuit to the motor. On his way back to the sump, he notified Employee #1 that the power was on. Arriving at the sump, the electrical mechanic did not see Employee #1 at the site. He went to his truck, which was parked approximately 30 feet west of the sump, and found it empty. Returning to the sump area, the electrical mechanic found Employee #1 face up in a small pond of water, approximately 10 feet from the sump. The electrical mechanic informed dispatch about the accident and quickly returned to the MCC room to deenergize the circuit to the motor and lock it out. After the electrical mechanic determined that the area around Employee #1 was not electrified, Employee #1 was pulled from the pond and administered CPR, until Weber County EMT arrived. Employee #1 apparently received an electric shock that caused his "hypertensive" heart to fibrillate, and he was killed. Upon request from the Deputy to the electrical mechanic, they found that the switch was in the "manual' position. Inspection of the pump revealed that two of the 480-volt, three-phase cable conductors were exposed and "shorted to the pump's steel house."

Keywords: ELECTRIC MOTOR, HEART, CPR, ELECTRIC CABLE, ELECTROCUTED, LOCKOUT, ELECTRIC CONDUCTOR, ELECTRIC SHOCK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 309172716 Fatality Electric Shock Helpers, mechanics and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.