Inspection: 309100121 - Sodexho Facilities Management

Inspection Information - Office: Mobile Area Office

 

Inspection Nr: 309100121
Report ID: 0418600
Date Opened: 05/27/2005

Site Address:
Sodexho Facilities Management
Tuskegee University
Tuskegee, AL 36088

Mailing Address:
, , 00000

Union Status: Union

SIC:8744

NAICS: 561210/Facilities Support Services


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/01/2005

Emphasis:

Case Closed: 12/19/2005


Related Activity
Type Activity Nr Safety Health
Accident 100452549
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 6 2 8
Current Violations 2 1 3
Initial Penalty $28,000 $0 $0 $1,000 $0 $29,000
Current Penalty $14,000 $0 $0 $0 $0 $14,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100132 A 11/16/2005 11/22/2005 $0 $7,000 $0 I - Informal Settlement Citation has been deleted.
2. 01002 Serious 19100303 H02 II 11/16/2005 11/22/2005 $0 $0 $0 I - Informal Settlement Citation has been deleted.
3. 01003 Serious 19100332 B01 11/16/2005 11/22/2005 $0 $7,000 $0 I - Informal Settlement Citation has been deleted.
4. 01004 Serious 19100333 C02 11/16/2005 11/22/2005 $0 $0 $0 I - Informal Settlement Citation has been deleted.
5. 01005A Serious 19100335 A01 I 11/16/2005 11/22/2005 $7,000 $7,000 $0 I - Informal Settlement  
6. 01005B Serious 19100303 H02 II 12/08/2005 12/09/2005 $0 $0 $0 -  
7. 01006A Serious 19100332 B01 11/16/2005 11/22/2005 $7,000 $7,000 $0 I - Informal Settlement  
8. 01006B Serious 19100333 C02 12/08/2005 12/09/2005 $0 $0 $0 -  
9. 02001 Other 19040032 B03 11/16/2005 11/22/2005 $0 $1,000 $0 I - Informal Settlement Citation has been deleted.
10. 02002 Other 19100147 C06 I 11/16/2005 11/22/2005 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 200451847
Event: 05/27/2005
Employee Is Electrocuted While Inspecting Capacitor Cabinet

On May 27, 2005, The Tuskegee University construction manager phoned Employee #1, the chief engineer for Sodexho Facilities Management. The University of Tuskegee contracted Sodexho to manage overall maintenance of campus facilities. The construction manager wanted to determine if 100-kVA (apparently 100 kilovolt amp) fuses were located on the 4-kVA capacitor electric distribution system. Employee #1 apparently did not know if fuses were present and agreed to meet the construction manager at the switch gear building, where the equipment was located. The construction manager, Employee #1, and the electric supervisor proceeded to the electric room, where the equipment was located. They opened the unlocked front side of the capacitor bank cabinet, where the fuses were supposed to be located, and did not observe any fuses. They then proceeded to the back side of the capacitor cabinet. They opened the back side of the cabinet and again did not observe any fuses. They proceeded back to the front side of the capacitor cabinet. While reexamining the inside of the capacitor cabinet, the construction manager pointed out what appeared to be fuse holders. Employee #1 apparently went down on his knees to read information printed on the fuse holders, while the construction manager called the consulting engineer to inform him of the absence of the fuses and the electric supervisor looked on. Employee #1, who was not insulated from the exposed, energized feeds and fuse holders, was electrocuted and killed when he contacted the 12,470-volt center phase of the system.

Keywords: ELECTROCUTED, CAPACITOR, ELECTRIC SHOCK, ELECTRICAL CABINET

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 309100121 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.