Powered by GoogleTranslate

Inspection Detail

Inspection: 309091874 - Potelco, Inc

Inspection Information - Office: Washington Area Office

 

Inspection Nr: 309091874
Report ID: 1032300
Date Opened: 04/30/2007

Site Address:
Potelco, Inc
Naval Base Kitsap - Bangor
Silverdale, WA 98315

Mailing Address:
14103 8th Street E, Sumner, WA 98390

Union Status: Union

SIC:1731

NAICS: 238210/Electrical Contractors


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/15/2007

Emphasis: S:Electrical

Case Closed: 07/21/2008


Related Activity
Type Activity Nr Safety Health
Accident 101580611
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 6 6
Current Violations 2 2
Initial Penalty $16,300 $0 $0 $0 $0 $16,300
Current Penalty $6,000 $0 $0 $0 $0 $6,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100269 C 06/25/2007 06/28/2007 $0 $1,800 $0 07/13/2007 F - Formal Settlement Citation has been deleted.
2. 01002 Serious 19100269 N03 06/25/2007 07/30/2007 $4,500 $2,250 $0 07/13/2007 F - Formal Settlement  
3. 01003 Serious 19100269 P04 I 06/25/2007 07/30/2007 $0 $4,500 $0 07/13/2007 F - Formal Settlement Citation has been deleted.
4. 01004 Serious 19100269 P04 II 06/25/2007 07/30/2007 $1,500 $4,500 $0 07/13/2007 F - Formal Settlement  
5. 01005 Serious 19100269 P04 III 06/25/2007 07/30/2007 $2,250 $2,250 $0 07/13/2007 F - Formal Settlement Citation has been deleted.
6. 01006 Serious 19100269 Q01 III 06/25/2007 07/30/2007 $1,000 $1,000 $0 07/13/2007 F - Formal Settlement Citation has been deleted.

Investigation Summary

Investigation Nr: 201580982
Event: 04/30/2007
EMPLOYEE ELECTROCUTED when derrick boom contacts electric li

On April 30, 2007, Employee #1, an apprentice, and coworkers were setting up a new wood pole for a 7200 kilovolt distribution line. They first drilled the hole with the insulated boom situated under the lines and at full extension. The crew then retracted the boom fully, making it uninsulated, and began to unload the replacement pole from the truck. While maneuvering the pole, the signalman allowed the boom to violate the approach distance of 25 in. The operator started to boom down and before the signalman could react, had touched one phase line. The operator immediately boomed back up, breaking the conductive path. At the moment of contact Employee #1 was moving around the truck to help the signalman. He was apparently trying to steady himself while climbing over a pallet of power cables, and had one hand on a grab bar of the truck and the other hand on a metal garage door. The electrical current entered the palm of Employee #1's left hand and exited through the fingers of his right hand. He was able to take one or two steps and respond to a question before collapsing. Coworkers and the responding paramedics administered CPR, but Employee #1 died.

Keywords: CLEARANCE, DERRICK TRUCK, OVERHEAD POWER LINE, SIGNALMAN, CPR, WORK RULES, ELECTROCUTED, STRUCK AGAINST, CONSTRUCTION, INATTENTION

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 309091874 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close