Inspection Detail
Inspection: 308593292 - Purcell Construction Inc.
Inspection Information - Office: Houston North Area Office
Site Address:
Purcell Construction Inc.
7909 Fry Road
Cypress, TX 77433
Mailing Address:
277 Dennis St, Humble, TX 77338
Union Status: NonUnion
SIC:1542
NAICS: 236220/Commercial and Institutional Building Construction
Inspection Type: Unprog Rel
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 07/14/2006
Emphasis:
Case Closed: 07/14/2006
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 101763498 |
Investigation Summary
On July 12, 2006, Employee #1, an apprentice electrician with approximately 18 months of experience, was using a fiberglass ladder to install 277-volt fluorescent lighting fixtures inside a suspended ceiling. The circuit was energized. He had already connected the neutral and ground conductors to the fixture. Employee #1 was beginning to strip the insulation from the energized conductor when his bare fingers contacted either the energized conductor or his energized wire strippers. He completed the path to ground when his side and upper chest contacted the grounded struts that supported the suspended ceiling. Employee #1 was electrocuted. His tools were not insulated, and he was not wearing any form of personal protective equipment.
Keywords: LIGHTING CIRCUIT, INSULATED TOOL, WORK RULES, INEXPERIENCE, ELEC PROTECT EQUIP, ELECTRICIAN, ELECTROCUTED, STRUCK AGAINST, CONSTRUCTION, ELEC CIRC PART--MISC
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 308593292 | Occupation not reported |
Translate