Powered by GoogleTranslate

Inspection Detail

Inspection: 308492792 - Ortiz Enterprises, Inc

Inspection Information - Office: Van Nuys Mining & Tunneling District Office

 

Inspection Nr: 308492792
Report ID: 0950652
Date Opened: 04/26/2005

Site Address:
Ortiz Enterprises, Inc
10051 W Black Mountain Rd
San Diego, CA 92126

Mailing Address:
6 Cushing, Suite 200, Irvine, CA 92618

Union Status: Union

SIC:1481

NAICS: 213115/Support Activities for Nonmetallic Minerals (except Fuels)


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 07/12/2005

Emphasis: L:Tunnel

Case Closed: 08/13/2008


Related Activity
Type Activity Nr Safety Health
Accident 362179988
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 3 2 6
Current Violations 4 2 6
Initial Penalty $10,125 $210,000 $0 $1,400 $0 $221,525
Current Penalty $85,125 $0 $0 $1,400 $0 $86,525
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 3203 A02 07/12/2005 07/30/2005 $800 $800 $0 07/15/2005 J - ALJ Decision  
2. 01002 Other 3314 G02 A 07/12/2005 07/30/2005 $600 $600 $0 07/15/2005 J - ALJ Decision  
3. 02001 Serious 3203 A06 07/12/2005 07/30/2005 $10,125 $10,125 $0 07/15/2005 J - ALJ Decision  
4. 03001 Serious 23200002 A 07/12/2005 07/30/2005 $25,000 $70,000 $0 07/15/2005 J - ALJ Decision  
5. 04001 Serious 23400001 07/12/2005 07/30/2005 $25,000 $70,000 $0 07/15/2005 J - ALJ Decision  
6. 05001 Serious 3203 A07 07/12/2005 07/30/2005 $25,000 $70,000 $0 07/15/2005 J - ALJ Decision  

Investigation Summary

Investigation Nr: 202422101
Event: 01/13/2005
Employee Is Electrocuted Resetting Circuit Breaker

At approximately 5:00 p.m. on January 13, 2005, Employee #1 was working at a portable rock crushing operation. He was sent into a trailer containing electrical equipment in order to reset the circuit breaker on a Saftronics 460 Volt motor controller, Model Number EZ6-240, Serial Number 114355. The circuit breaker was contained in a 3 ft by 5 ft enclosure. There was a handle on the door which, through a mechanical linkage, can be used to turn the circuit breaker on and off. This mechanical linkage was not operable, requiring a worker to reach into the enclosure and reset the breaker by hand. This would expose a worker to numerous possible contact points energized to 460 volts A.C. Further, the mechanism was broken such that the door itself would not latch closed. A second handle which would keep the door closed was also broken. Under normal operating conditions, the door would not be opened until the handle was turned to the position which turns the circuit breaker off. The door latch had been broken for approximately 5 months. The foreman personally showed Employee #1 how to reset the breaker by hand. This procedure would happen three to five times per week. Employee #1 was found in the trailer unconscious. He was taken to a hospital and pronounced dead due to electrocution.

Keywords: ELECTRIC ARC, ELECTROCUTED, LOCKOUT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 308492792 Fatality Electric Shock Laborers, except construction
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close