Inspection Detail
Inspection: 308465343 - Sunrise Electric Of Central Florida, Inc.
Inspection Information - Office: Tampa Area Office
Site Address:
Sunrise Electric Of Central Florida, Inc.
200 N. Lakemont Ave.
Winter Park, FL 32792
Mailing Address:
1708 Old River Trail, Chuluota, FL 32766
Union Status: NonUnion
SIC:1731
NAICS: 238210/Electrical Contractors
Inspection Type: Accident
Scope: Complete
Advanced Notice: Y
Ownership: Private
Safety/Health: Safety
Close Conference: 04/07/2005
Emphasis:
Case Closed: 10/06/2005
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 102435807 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 2 | 2 | ||||
Current Violations | 2 | 2 | ||||
Initial Penalty | $9,800 | $0 | $0 | $0 | $0 | $9,800 |
Current Penalty | $7,350 | $0 | $0 | $0 | $0 | $7,350 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001A | Serious | 19260416 A01 | 04/08/2005 | 04/13/2005 | $3,675 | $4,900 | $0 | I - Informal Settlement | ||
2. | 01001B | Serious | 19260095 A | 04/08/2005 | 04/13/2005 | $0 | $0 | $0 | I - Informal Settlement | ||
3. | 01002A | Serious | 19260416 A03 | 04/08/2005 | 04/13/2005 | $3,675 | $4,900 | $0 | I - Informal Settlement | ||
4. | 01002B | Serious | 19260021 B02 | 04/08/2005 | 04/13/2005 | $0 | $0 | $0 | I - Informal Settlement |
Investigation Summary
At approximately 7:00 a.m. on December 15, 2004, Employees #1 through #3, all electricians, were working in the electrical utility room of a hospital. Their employer had been contracted to switch the power to an electrical panel from a 200-amp plug-in bus in the utility room (connected to a 3,000-amp busway) to a main distribution panel two floors up. The plug-in had been switched off and tested, and the fuses had been removed, but the plug-in was still connected to the energized busway. Just before the power to the existing panel was turned on, there was an explosion. None of the employees was working at the plug-in, but Employee #1 was closest to the busway. He suffered severe burns and was killed. Employee #2, the next closest, sustained second-degree burns to his face, chest, arms, and back. He was transported to a local burn center for treatment. Employee #3 suffered only minor burns, but he was knocked out the door of the electrical room. He sustained injuries that did not require hospitalization.
Keywords: BURN, ELECTRICAL, ELECTRICIAN, CONSTRUCTION, ELECTRICAL WORK, EXPLOSION, ELEC CIRC PART--MISC, ELECTRICAL CABINET, ELECTRICAL FAULT, FACE
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 308465343 | Fatality | Burn/Scald(Heat) | Electricians | ||
2 | 308465343 | Hospitalized injury | Burn/Scald(Heat) | Electricians' apprentices | ||
3 | 308465343 | Non Hospitalized injury | Cut/Laceration | Electricians |