Inspection Information - Office: Dosh Tumwater Service Location, Tumwater, Wa

 

Inspection Nr: 308072784
Report ID: 1055340
Date Opened: 10/06/2004

Site Address:
Bridgewood At Four Seasons Llc
11700 Ne Angelo Dr
Vancouver, WA 98684

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:8361

NAICS: 623312/Homes for the Elderly


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 03/16/2005

Emphasis: L:Walep

Case Closed: 07/20/2005


Related Activity
Type Activity Nr Safety Health
Accident 101197853
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1 2
Current Violations
Initial Penalty $300 $0 $0 $0 $0 $300
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 80014005 03/31/2005 05/03/2005 $0 $300 $0 04/18/2005 Y - State Decision Citation has been deleted.
2. 02001 Other 80028022 03/31/2005 06/02/2005 $0 $0 $0 04/18/2005 Y - State Decision Citation has been deleted.

Investigation Summary

Investigation Nr: 202364329
Event: 10/05/2004
Employee Is Electrocuted While Changing Light Bulb

Employee #1, a maintenance worker, was changing a metal halide light bulb in a recessed ceiling fixture. While unscrewing the bulb, he broke the glass globe and exposed the filament. He then traced the electrical circuit to a breaker box using plans supplied by the building contractor, and turned off the breaker. He then accessed the attic, removed the can from the fixture, and without testing for the presence of electrical power, attempted to remove the filament with uninsulated pliers. However, the light was not on the circuit that was turned off and was still energized. He had one hand on the fixture housing, which was grounded, and when he contacted the filament with the pliers, which was energized, he completed the circuit and was electrocuted.

Keywords: SHOCK, ELECTRICAL, ELECTROCUTED, LIGHTING FIXTURE, CIRCUIT BREAKER, ELECTRIC SHOCK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 308072784 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.