Powered by GoogleTranslate

Inspection Detail

Inspection: 307994442 - Beecorp Inc. Dba Harris Electric

Inspection Information - Office: Tampa Area Office

 

Inspection Nr: 307994442
Report ID: 0420600
Date Opened: 09/15/2004

Site Address:
Beecorp Inc. Dba Harris Electric
3225 State Road 630, West
Ft. Meade, FL 33841

Mailing Address:
4619 Valleyview Dr., W., Lakeland, FL 33813

Union Status: NonUnion

SIC:1731

NAICS: 238210/Electrical Contractors


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 03/10/2005

Emphasis:

Case Closed: 01/16/2007


Related Activity
Type Activity Nr Safety Health
Accident 102424876
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 4 4
Current Violations 3 3
Initial Penalty $19,600 $0 $0 $0 $0 $19,600
Current Penalty $8,000 $0 $0 $0 $0 $8,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100269 A02 03/10/2005 03/29/2005 $3,000 $4,900 $0 03/28/2005 F - Formal Settlement  
2. 01002 Serious 19100269 C 03/10/2005 03/16/2005 $0 $4,900 $0 03/28/2005 F - Formal Settlement Citation has been deleted.
3. 01003 Serious 19100269 L02 03/10/2005 03/16/2005 $3,000 $4,900 $0 03/28/2005 F - Formal Settlement  
4. 01004 Serious 19100269 L06 III 03/10/2005 03/22/2005 $2,000 $4,900 $0 03/28/2005 F - Formal Settlement  

Investigation Summary

Investigation Nr: 202344552
Event: 09/11/2004
Employee dies after voltage meter causes arc flash

On September 11, 2004, Employee #1 was part of a work crew replacing a transformer that had been damaged by Hurricane Frances. He was using a handheld volt-ohm meter to measure buss voltage when an arc flash set his shirt on fire, severely burning his chest. He died three days later. Employee #1 was trying to measure a buss voltage of 4,160 volts, but the handheld unit would not safely measure more than 1,000 volts.

Keywords: BURN, CHEST, CLOTHING, ELECTRIC ARC, MAINTENANCE, ELECTRICAL, WORK RULES, CONSTRUCTION, TEST EQUIPMENT, HAND TOOL

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 307994442 Fatality Burn/Scald(Heat) Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close