Powered by GoogleTranslate

Inspection Detail

Inspection: 307837013 - Abitibi-Consolidated, Augusta News Print

Inspection Information - Office: Atlanta East Area Office

 

Inspection Nr: 307837013
Report ID: 0418100
Date Opened: 01/19/2005

Site Address:
Abitibi-Consolidated, Augusta News Print
2434 Doug Barnard Park
Augusta, GA 30906

Mailing Address:
P.O. Box 1647, Augusta, GA 30913

Union Status: Union

SIC:2621

NAICS: 322122/Newsprint Mills


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 01/20/2005

Emphasis:

Case Closed: 07/05/2005


Related Activity
Type Activity Nr Safety Health
Accident 101282275
Complaint 205148711 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 1 3
Current Violations 2 1 3
Initial Penalty $9,000 $0 $0 $4,500 $0 $13,500
Current Penalty $9,000 $0 $0 $0 $0 $9,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100334 C03 06/15/2005 06/20/2005 $4,500 $4,500 $0 I - Informal Settlement  
2. 01002 Serious 19100335 A01 I 06/15/2005 07/12/2005 $4,500 $4,500 $0 I - Informal Settlement  
3. 02001 Other 19040039 A 06/15/2005 06/20/2005 $0 $4,500 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 201281946
Event: 01/18/2005
Employee Is Burned by Arc Flash

On January 18, 2005, Employee #1 and two coworkers were trouble shooting the circuitry of a vacuum pump starter. The problem was determined to be inside the 4,160 volt motor switch gear. Employee #1 deenergized the gear and opened the cabinet. He depressed the breaker handle safety button and reenergized the gear with the cabinet open. After using a Fluke 87, rated for up to 1,000 volts, to test the primary side of the two 4,160 volt phases, an arc flash occurred. Employee #1 was hospitalized with burns to thirty percent of his body.

Keywords: ELECTRIC ARC, ELEC EQUIPMENT--MISC

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 307837013 Hospitalized injury Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close