Powered by GoogleTranslate

Occupational Safety and Health Administration OSHA

Inspection Detail

Inspection: 307659797 - Consolidated Edison Co. Of New York, Inc.

Inspection Information - Office: Tarrytown

 

Inspection Nr: 307659797
Report ID: 0216000
Date Opened: 06/23/2004

Site Address:
Consolidated Edison Co. Of New York, Inc.
1561 Central Park Ave
Yonkers, NY 10710

Mailing Address:
4 Irving Place - Room 819, New York, NY 10003

Union Status: Union

SIC:4911

NAICS: 221119/Other Electric Power Generation


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 12/06/2004

Emphasis:

Case Closed: 08/24/2005


Related Activity
Type Activity Nr Safety Health
Accident 102030889
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 5 5
Current Violations 5 5
Initial Penalty $35,000 $0 $0 $0 $0 $35,000
Current Penalty $35,000 $0 $0 $0 $0 $35,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19100269 A02 I 12/08/2004 12/13/2004 $7,000 $7,000 $0 12/27/2004 F - Formal Settlement  
2. 01001B Serious 19100269 A02 III 12/08/2004 12/13/2004 $0 $0 $0 12/27/2004 F - Formal Settlement  
3. 01002 Serious 19100269 C 12/08/2004 12/13/2004 $7,000 $7,000 $0 12/27/2004 F - Formal Settlement  
4. 01003 Serious 19100269 E01 12/08/2004 12/13/2004 $7,000 $7,000 $0 12/27/2004 F - Formal Settlement  
5. 01004 Serious 19100269 L06 III 12/08/2004 12/13/2004 $7,000 $7,000 $0 12/27/2004 F - Formal Settlement  
6. 01005 Serious 19100269 T07 12/08/2004 12/13/2004 $7,000 $7,000 $0 12/27/2004 F - Formal Settlement  

Investigation Summary

Investigation Nr: 202014049
Event: 06/23/2004
Burn - Electrical Fault In Underground Cable

Two crews and a supervisor were connecting a secondary main. One crew was making a connection in a service box south of a manhole. The other crew was making a connection in the manhole. The manhole crew discovered oil on the ground, probably from a leaking cable or joint. The crew also noticed that several feeders in the manhole were already wrapped with sorbent pads and plastic. The supervisor reported the conditions, and the crew was going to rewrap all the feeders, take a sample, and have the manhole cleaned before connecting the secondary main. Two workers entered the manhole and began wrapping the energized feeders. During the rewrapping process, one of the feeders faulted. The ensuing electric arc severely burned the two workers. One of them was able to get out of the manhole on his own, and emergency personnel removed the other injured worker. Both injured workers died several days later from complications related to their injuries. Three other workers on the scene, including two emergency responders, were treated for smoke inhalation. Several other workers were treated for trauma. (None of the nonfatally injured employees were listed on injury lines on the original form.) Investigation revealed that employees in one division of the electric utility were regularly wrapping leaky feeder cables and joints while they were energized. According to the utility, that activity had been going on for years unbeknownst to higher levels in the company. Apparently, that division misinterpreted company policy regarding work on energized cables.

Keywords:burn, electric arc, electrical, power line worker, ppe, lockout, e ptd, elec utility work, electrical fault, undrgrd power line

Investigated Inspection
# Inspection Age Sex Degree Nature Occupation
1 307659797 Fatality Burn/Scald(Heat) Electrical power installers and repairers
2 307659797 Fatality Burn/Scald(Heat) Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.