Powered by GoogleTranslate

Inspection Detail

Inspection: 307631416 - Current Communications, Llc

Inspection Information - Office: Long Island Area Office

 

Inspection Nr: 307631416
Report ID: 0214700
Date Opened: 06/08/2005

Site Address:
Current Communications, Llc
445 Commack Road
Commack, NY 11725

Mailing Address:
217 Pacific Street, Massapequa Park, NY 11762

Union Status: NonUnion

SIC:1731

NAICS: 238210/Electrical Contractors


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/21/2005

Emphasis:

Case Closed: 02/16/2006


Related Activity
Type Activity Nr Safety Health
Accident 100151273
Referral 200155828 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $1,500 $0 $0 $0 $0 $1,500
Current Penalty $900 $0 $0 $0 $0 $900
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100333 A 12/06/2005 12/13/2005 $900 $1,500 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 200150977
Event: 06/08/2005
Employee electrocuted while servicing panel box

On June 8, 2005, Employee #1, of Current Communications, LLC, was working alone in the power room of the Verizon Commack Central Office. He had been assigned to remove six 100-amp circuit breakers and their associated shielded conduits. There were no eyewitnesses to the event, but a telephone company worker found Employee #1 lying on the floor, dead, apparently the victim of an electric shock. The 800-amp electrical panel box remained energized during the removal process. Employee #1 was not wearing personal protective equipment, and no insulating material was wrapped around the energized bus bar. At the time of the accident, he had removed five of the six circuits.

Keywords: ELEC PROTECT EQUIP, ELECTRICAL, ELECTROCUTED, CONSTRUCTION, ELECTRICAL WORK, ELEC CIRC PART--MISC, ELECTRICAL BOX

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 307631416 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.