Inspection Detail
Inspection: 307564716 - Elliot Electric/Kentucky, Inc.
Inspection Information - Office: Ky Labor Cabinet Division Of Osh Compliance
Site Address:
Elliot Electric/Kentucky, Inc.
724 Woodford Dr
Mount Sterling, KY 40353
Mailing Address:
951 Enterprise Dr, Lexington, KY 40510
Union Status: NonUnion
SIC:1731
NAICS: 238210/Electrical Contractors
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 08/03/2004
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 12/15/2012
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 101867653 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 3 | 3 | ||||
Current Violations | 3 | 3 | ||||
Initial Penalty | $12,000 | $0 | $0 | $0 | $0 | $12,000 |
Current Penalty | $12,000 | $0 | $0 | $0 | $0 | $12,000 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 19260403 H | 09/13/2004 | 09/30/2004 | $4,000 | $4,000 | $0 | 09/23/2004 | - | |
2. | 01002A | Serious | 19260416 A01 | 09/13/2004 | 09/17/2004 | $4,000 | $4,000 | $0 | 09/23/2004 | - | |
3. | 01002B | Serious | 19260416 A03 | 09/13/2004 | 09/17/2004 | $0 | $0 | $0 | 09/23/2004 | - | |
4. | 01003 | Serious | 19260417 C | 09/13/2004 | 09/17/2004 | $4,000 | $4,000 | $0 | 09/23/2004 | - |
Investigation Summary
On July 21, 2004, Employee #1 turned off breaker #22 in a panel box so that he could make a connection in a junction box. He was using a wire stripper to cut into the insulation around a conductor when he was electrocuted. The breakers in the panel box were not labeled, and breaker #22 did not control the current in the circuit on which Employee #1 was preparing to work. He also did not use a volt meter or another type of instrument to test the circuit and confirm that the power was off.
Keywords: INSTALLING, ELECTRICAL, ELECTRICAL TESTING, WORK RULES, ELECTROCUTED, CONSTRUCTION, ELECTRICAL WORK, TEST EQUIPMENT, CIRCUIT BREAKER, ELEC CIRC PART--MISC
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 307564716 | Fatality | Electric Shock | Electricians |