Powered by GoogleTranslate

Inspection Detail

Inspection: 307462317 - Southern California Edison

Inspection Information - Office: San Bernardino District Office

 

Inspection Nr: 307462317
Report ID: 0950633
Date Opened: 02/22/2007

Site Address:
Southern California Edison
37000 E.Santa Fe St
Daggett, CA 92327

Mailing Address:
14660 Chestnut Ave, Westminster, CA 92683

Union Status: Union

SIC:4911

NAICS: 221122/Electric Power Distribution


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/13/2007

Emphasis:

Case Closed: 10/01/2007


Related Activity
Type Activity Nr Safety Health
Accident 102493368
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 1 1 2
Initial Penalty $21,375 $0 $0 $0 $0 $21,375
Current Penalty $2,700 $0 $0 $0 $0 $2,700
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 3203 A02 06/13/2007 06/20/2007 $0 $3,375 $0 07/02/2007 F - Formal Settlement  
2. 02001 Serious 2941 H11 06/13/2007 06/20/2007 $2,700 $18,000 $0 07/02/2007 F - Formal Settlement  

Investigation Summary

Investigation Nr: 202445490
Event: 01/03/2007
Employee's Hand Is Burned Due to Electrical Shock

At approximately 12:30 p.m. on January 3, 2007, Employee #1, a foreman, and a crew of nine were replacing a deteriorated wooden H-frame structure carrying 115 kV overhead power lines. There were three conductors with light weight tubular steel poles. There was an energized high voltage line 230 kV approximately 60 ft from the de energized conductors. All the conductors were deenergized and were resting on the ground. Employee #1 and a coworker, an apprentice, were trying to put the center phase conductor on the suspension shoe on the crossarm. Employee #1 was in the basket of a crane, Altec 92 foote crane, and the conductor was on the hook of the crane, a Y2K Electric line truck-crane. The boom of the electric truck was not long enough to reach the suspension shoe. Employee #1 was holding the hook of the lift in one hand and the conductor in the other hand. He placed himself between two different ground potentials due to induced voltage caused by the 230KV power lines. He received a severe shock which caused second and third degree burns on both hands, which required hospitalization.

Keywords: BURN, ELECTRIC SHOCK, HAND

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 307462317 Hospitalized injury Electric Shock Supervisors; electricians & power transm. install.
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.